11 changing password, 12 setting bacnet ms/tp – E-Mon E-D5-600800-S*SPL3-V3KIT3 User Manual

Page 47

Advertising
background image

DIN-MON™ SMART METER

47

62-0442—04

7.2.11 Changing Password

To change the Password, complete the following steps:

1. Press MENU button.

2. Use UP or DOWN button until the arrow is on the

PASSWORD line.

3. Press SELECT button.

4. Use UP or DOWN button to make changes.

5. Press SELECT button to advance to the next setting. Repeat this step until all

the password settings have been updated.

6. Press MENU to complete the changes. If changes were made, you’ll be asked to

save changes.

7. Press UP or DOWN to select ‘Y’ or ‘N’.

8. Press SELECT button to accept the selection. This will return you to the main

menu.

9. Select EXIT to get out of programming mode and return to normal display mode.

*status: <Pwd change OK>, <Pwd not changed>, <Pwd Reset OK>

FIELD RANGE: OLD password=[0000..9999], NEW password=[0000..9999];

7.2.12 Setting BACnet MS/TP

To change the BACnet setting, complete the following

steps:

1. Press MENU button.

2. Use UP or DOWN button until the arrow is on the

BACNET SETTINGS line.

3. Press SELECT button.

Use

UP or DOWN button to make changes.

To change by digit, refer to note in Section 7.1 Navigating Menus.

4. Press SELECT button to advance to the next setting. Repeat this step until all

the BACnet settings have been updated.

5. Press MENU to complete the changes. If changes were made, you’ll be asked to

save changes.

6. Press UP or DOWN to select ‘Y’ or ‘N’.

7. Press SELECT button to accept the selection. This will return you to the main

menu.

8. Select EXIT to get out of programming mode and return to normal display mode.

FIELD RANGE: MSTP MAC=[0..127]; MAX MASTER=[1..127]

OLD

0000

NEW

0000

CONFIRM

Y

MSTP MAC

1

MAX MASTER

127

PORT

47808