Important, Caution, Wiring – Yokogawa ADMAG AXF User Manual

Page 48: Axfa11 converter

Advertising
background image

IM 01E20D01-01E

4-14

4. WIRING

(5) Wiring the Remote Flowtube (General-

Purpose Use, Submersible Type, Size 500
to 1000 mm (20 to 40 in.)) with Converters

1) Connection with the AXFA11 converter

Connect wiring as shown in the figure below.

I+

4-20mA out

Shortbar

I–

CURRENT OUT

AL+

AL–

C

SA

A

B

SB

ALARM OUT

N/–

L/+

POWER SUPPLY

EX2

EX1

EXCIT ATION

P–

SI1+

SI2+

COM

P+

PULSE OUT

STATUS IN

SIGNAL

SO1+

COM

SO2+

STATUS OUT

FUSE

2.5A 250V

AXFA11 converter

Converter

Remote

flowtube

F040217.EPS

SA

A
B

SB

C

EX1
EX2

Taping*

A
B

Taping*

C

EX1
EX2

* Individually tape and insulate

the shields corresponding to SA
and SB on the remote flowtube
side.

Remote flowtube

EX2

Excitation
cable

EX1

A

B

C

AXFC dedicated
signal cable

Figure 4.2.17 Wiring Diagram

IMPORTANT

A remote flowtube (size 500 to 1000 mm) cannot
be combined with AXFA14 converter.

(6) Wiring the Remote Flowtube (General-

Purpose Use, Submersible Type, Size 1100
to 2600 mm (44 to 104 in.)) with Convert-
ers

1) Connection with the AXFA11 converter

Connect wiring as shown in the figure below.

I+

4-20mA out

I–

CURRENT OUT

AL+

AL–

C

SA

A

B

SB

ALARM OUT

N/–

L/+

POWER SUPPLY

EX2

EX1

EXCIT ATION

P–

SI1+

SI2+

COM

P+

PULSE OUT

STATUS IN

SIGNAL

SO1+

COM

SO2+

STATUS OUT

FUSE

2.5A 250V

Shortbar

F040218.EPS

AXFA11 converter

Converter

Remote

flowtube

SA

A
B

SB

C

EX1
EX2

Taping*

A
B

Taping*

C

EX1
EX2

* Individually tape and insulate

the shields corresponding to SA
and SB on the remote flowtube
side.

Remote flowtube

AXFC dedicated
signal cable

EX2

EX1

A

B

C

Excitation
cable

Figure 4.2.18 Wiring Diagram

IMPORTANT

A remote flowtube (size 1100 to 2600 mm)
cannot be combined with AXFA14 converter.

(7) Grounding

CAUTION

Be sure to connect the protective grounding of
the AXF remote flowtube with a cable of 2mm

2

or larger cross section in order to avoid electrical
shock to the operators and maintenance engi-
neers and to prevent the influence of external
noise.
Connect the grounding wire to the

mark.

The grounding should satisfy Class D require-
ments (ground resistance, 100

⍀ or less).

In case of TIIS Flameproof type, the grounding
should satisfy Class C requirements (ground
resistance, 10

⍀ or less) or class A requirements

(ground resistance, 10

⍀ or less).

For explosion proof type except TIIS, follow the
domestic electrical requirements as regulated in
each country.

IMPORTANT

Improper grounding can have an adverse affect
on the flow measurement. Ensure that the
instrument is properly grounded.