App index, Xj sets an rjc, Wu sets environment settings – Yokogawa Button Operated MV2000 User Manual

Page 103

Advertising
background image

4-29

Commands

IM MV1000-17E

1

2

3

4

5

6

7

App

Index

Description Set parameter p1 according to the table in

section 4.3.

XJ

Sets an RJC

To use the internal compensation circuit

Syntax

XJ p1,p2<terminator>
p1 Measurement channel number
p2 Reference junction compensation

designation (INTERNAL)

Query

XJ[ p1]?

Example Set the channel 001 RJC to the internal

compensation circuit.
XJ001,INTERNAL

To use an external RJC

Syntax

XJ p1,p2,p3<terminator>
p1 Measurement channel number
p2 Reference junction compensation

designation (EXTERNAL)

p3 External RJC value (–20000 to 20000)

Query

XJ[ p1]?

Example Set the channel 002 RJC to external and set the

compensation value to 0 μV.
XJ002,EXTERNAL,0

Description • Set parameter p1 according to the table in

section 4.3.

• The unit of parameter p3 is μV.

WU

Sets environment settings

Setup items

GENERAL,BATCH,DISPLAY,MESSAGE,INPUT,

ALARM,SECURITY,MEDIA,MATH,REPORT,
SERVICEPORT,DECIMALPOINT,POP3

General environment settings

Syntax

WU p1,p2,p3<terminator>
p1 Setting type (GENERAL)
p2 Tag/channel number selection

TAG
CHANNEL Channel number

p3 Language

ENGLISH
JAPANESE
CHINESE
GERMAN
FRENCH
KOREAN

Example Select tag display and set the language to

English.
WUGENERAL,TAG,ENGLISH

To set the batch function

Syntax

WU p1,p2,p3,p4<terminator>
p1 Setting type (BATCH)
p2 Batch function ON/OFF
p3 Number of lot number digits (OFF, 4, 6, 8)
p4 Auto increment ON/OFF

Description Parameters p3 and p4 are valid only when p2 is

ON.

To set the display

Syntax

WU p1,p2<terminator>
p1 Setting type (DISPLAY)
p2 Trend type (T-Y)
p3 Partial expansion ON/OFF
p4 Trend interval switching ON/OFF

To set message settings

Syntax

WU p1,p2,p3,p4<terminator>
p1 Setting type (MESSAGE)
p2 Method of writing messages from keys

COMMON Applied to all display groups
SEPARATE Applied to a specified display

group

p3 Power failure message ON/OFF
p4 Change message ON/OFF

To set the input

Syntax

WU p1,p2<terminator>
p1 Setting type (INPUT)
p2 Detection of values exceeding the scale

FREE

When the measurement range is
exceeded

OVER

When ±105% of the scale is
exceeded

To set alarm settings

Syntax

WU p1,p2<terminator>
p1 Setting type (ALARM)
p2 Alarm suppression function ON/OFF

To set security settings

Syntax

WU p1,p2,p3<terminator>
p1 Setting type (SECURITY)
p2 Keys

OFF

Disable security

KEYLOCK Lock the keys
LOGIN Enable the login function

p3 Communication

OFF

Disable security

LOGIN Enable the login function

Set media settings

Syntax

WU p1,p2,p3<terminator>
p1 Setting type (MEDIA)
p2 Auto save function ON/OFF
p3 Media FIFO ON/OFF

Example Use media FIFO.

WUMEDIA,ON,ON

Description Parameter p3 is valid only when p2 is ON.

4.6 Basic Setting Commands

Advertising
This manual is related to the following products: