Message Summary

• The MV returns the message summary in response to an FL command.
• The MV retains a maximum of 100 messages. Messages that exceed 100 are cleared

from the oldest ones.

• Syntax

EACRLF
yy/mo/dd_hh:mm:ss_mmm···_ggg···_zzz_uuu···_nnn···CRLF
···································
ENCRLF

yy Year (00 to 99)
mo Month (01 to 12)
dd Day (01 to 31)
hh Hour (00 to 23)
mm Minute (00 to 59)
ss Second (00 to 59)
mmm··· Message (32 characters. Spaces are padded when the number of

characters is less than 32 characters.)

ggg··· Message write destination group (11 characters)

xx,xx,xx,xx:

Displays groups that have message written in, each
group separated by a comma (up to four groups)

ALL:

All groups

zzz Operation property

KEY: Key operation
COM: Communication
REM: Remote
ACT: Event action
SYS: System

uuu··· User name (up to 20 characters)
nnn··· Message sequence number (0 for add messages)
_ Space

• Example

EA
01/05/11 12:20:00 operation-start

01,02,03,04 KEY admin 11

01/05/11 12:20:00 operation-start

01,02 KEY admin 11

01/05/11 12:20:00*0123456789abcdefg 01,02,03,04 KEY admin 12