4-21

Commands

IM MV1000-17E

1

2

3

4

5

6

7

App

Index

Example Set the first menu item to TREND and the

second menu item to TRENDHISTORY.
SMDISP_MAIN,TREND,TRENDHISTORY,

Description • If you omit parameters p2 and subsequent

parameters, all menus items will be hidden.

• A command error will occur if you specify the

same menu item multiple times.

• You can specify up to three separators. If you

specify more than three, an error will occur.

• You cannot omit parameters by using

delimiters (, ,).

• 4PANEL is available only on the MV2000.
• If you set the first menu item to SEPARATOR,

it will be ignored.

To set a submenu

Syntax

SM p1,p2,p3,....<terminator>
p1 Type (DISP_SUB)
p2 Menu type (TREND, DIGITAL, BAR,

TRENDHISTORY, OVERVIEW,
INFORMATION, LOG, 4PANEL)

p3 and up

Menu items to be displayed in the submenu

The items are displayed in the specified
order.

Only the specified menu items are
displayed.

If p2 is

TREND [select from the items below]

GROUP1–GROUP36 Group designation
ALL_CHANNEL

All channel display

SCALE

Scale display

DIGITAL

Digital display

MESSAGE_DISP

Message display

TREND_SPACE

Trend space

AUTO

Auto switching

EXPAND
SEPARATOR
FINE_GRID

Fine grid ON/OFF

AUTO_ZONE

Auto zone display/
normal display

If p2 is

DIGITAL [select from the items

below]
GROUP1–GROUP36 Group designation
AUTO

Auto switching

EXPAND
SEPARATOR

If p2 is

BAR [select from the items below]

GROUP1–GROUP36 Group designation
AUTO

Auto switching

EXPAND
SEPARATOR

If p2 is

TRENDHISTORY [select from the

items below]
GROUP1–GROUP36 Group designation
SEPARATOR

If p2 is

OVERVIEW [select from the items

below]
CURSOR

Cursor display

TO_ALARM

To alarm summary

TO_TREND

To trend display

TO_DIGITAL

To digital display

TO_BAR

To bar graph display

EXPAND
SEPARATOR

If p2 is

INFORMATION [select from the items

below]
ALARM

Alarm summary

MESSAGE

Message summary

MEMORY

Memory summary

MODBUS_CLIENT

ModbusTCP status
display

MODBUS_MASTER

ModbusRTU status
display

RELAY

Relay status display

REPORT

Report display

TO_HISTORY

To historical display

TO_HISTORY_D

To historical (display)

TO_HISTORY_E

To historical (event)

TO_OVERVIEW

To overview display

SORT_KEY

Switch the sort key

SORT_ORDER

Switch the sort order

DISP_ITEM

Switch Date/
Username

DATA_KIND

Switch the data type

DATE/FILE

Switch Date/
Filename

SELECT_SAVE

Select save

REPORT_CHANNEL Switch the report

channel display

ALL_SAVE
MANUAL_SAVE

Save manual sample

REPORT_SAVE

Save report

EXPAND
SEPARATOR
DATA_SAVE_MODE Data save mode
COLUMN_BAR

Stacked bar graph

COLUMN_BAR_DISP 1-column display/2-

column display

COLUMN_BAR_SELECT

Select a bar graph/
select a group

REPORT_GROUP1–GROUP6

Select a report group
on the MV2000

REPORT_GROUP1–GROUP4

Select a report group
on the MV1000

If p2 is

LOG [select from the items below]

LOGIN_LOG

Login log

ERROR_LOG

Error log

COMMU_LOG

Communication log

FTP_LOG

FTP log

WEB_LOG

Web log

MAIL_LOG

E-mail log

SNTP_LOG

SNTP log

4.4 Setting Commands (Setting)

Advertising