Modbus Server Function

Modbus Server Specifications

Communication available via ModbusTCP
Communication media: Ethernet 10Base-T
Port:

502/tcp (default value)

Command wait timeout: 1 minute. However, the timeout to receive the entire command

after starting to receive a command is 10 seconds.

Maximum number of connections: 2
Supported functions:

The table below contain functions that the MV supports.

Function
Code

Function

Operation

3

Reads the hold register

(4XXXX)

The client device reads the communication input

data and external input channel data from the MV.

4

Reads the input register

(3XXXX)

The client device reads the computed, measured,

alarm, and time data from the MV.

6

Writes once to hold

register (4XXXX)

The client device writes data to the

communication input channel and external input

channel on the MV.

8

Loopback test

The client device performs a loopback test on the

MV.

16

Writes to hold register

(4XXXX)

The client device writes data to the

communication input channel and external input

channel on the MV.

Register Assignments (shared with the Modbus slave function)

Measurement channel

Computation channel

External input channel

Measurement channel

Computation channel

External input channel

Time

Measured data

Alarm status

Computed data

Alarm status

Measured data

Alarm status

Alarm list

Alarm list

Alarm list

Data type

16-bit signed integer

Bit string

32-bit signed integer

Bit string

16-bit signed integer

Bit string

Bit string

Bit string

Bit string

16-bit signed integer

Number

30001 to 30048

31001 to 31048

32001 to 32120

33001 to 33060

34001 to 34240

35001 to 35240

36001 to 36012

36021 to 36035

36041 to 36100

39001 to 39008

Data type

MV input register

Communication input data

Measured data of external input channel

Data type

16-bit signed integer

32-bit floating point

16-bit signed integer

Number

40001 to 40060

40301 to 40420

41001 to 41240

Data type

MV hold register

Client

Read

Client

Read

Write

7.3 Modbus Protocol Specifications