App index, Yv sets e-mail recipient addresses, Yw sets the e-mail sender address – Yokogawa Button Operated MV2000 User Manual

Page 109: Yx sets the e-mail smtp server name, Yj sets a modbus client destination server, Yp sets basic modbus client settings, Yr sets a modbus client transmission command

Advertising
background image

4-35

Commands

IM MV1000-17E

1

2

3

4

5

6

7

App

Index

p3 Recipient 2 ON/OFF
p4 Include source URL ON/OFF
p5 Subject (up to 32 alphanumeric characters)
p6 Header 1 (up to 64 characters)
p7 Header 2 (up to 64 characters)

Query

YU[ p1]?

Example Send report generation notification e-mail

messages including the source URL to recipient
1. Set the subject to “Report” and header 1 to
“LP2.”
YUREPORT,ON,OFF,ON,Report,LP2

Description • For the contents of system notifications, see

section 2.3.

• Report generation notification can be used on

models with the /M1 math option.

• For e-mail settings, see section 2.3.

YV

Sets e-mail recipient addresses

Syntax

YV p1,p2<terminator>
p1 Recipient selection

1

Recipient 1

2

Recipient 2

p2 Recipient address (up to 150 alphanumeric

characters)

Query

YV[p1]?

Example Set recipient 1 to “[email protected]

and “[email protected].”
YV1,[email protected] mvuser2@
daqstation.com

Description • To set multiple recipients, separate each

recipient with a space.

• For e-mail settings, see section 2.3.

YW

Sets the e-mail sender address

Syntax

YW p1<terminator>
p1 Sender address (up to 64 alphanumeric

characters)

Query

YW?

Example Set the sender address to “mvadv.”

YWmvadv

Description For e-mail settings, see section 2.3.

YX

Sets the e-mail SMTP server

name

Syntax

YX p1,p2,p3<terminator>
p1 SMTP server name (up to 64 characters)
p2 Port number (0 to 65535)
p3 Authentication

OFF

No authentication

POPBEFORESMTP

Execute POP Before
SMTP

Query

YX?

Example Set the SMTP server to “smtp.daqstation.com,”

the port number to “25,” and execute POP
Before SMTP.
YX smtp.daqstation.com,25,POPBEFORESMTP

Description For e-mail settings, see section 2.4.

YJ

Sets a Modbus client destination

server

Syntax

YJ p1,p2,p3,p4,p5<terminator>

p1 Server number (1 to 16)
p2 Port number (0 to 65535)
p3 Host name (up to 64 characters)
p4 Unit number registration

AUTO

Not use the unit number

FIXED Use a fixed unit number

p5 Unit number (0 to 255)

Query

YJ[ p1]?

Example Set the port number of server number 3 to 502,

the host name to mv2000, the unit number
registration to FIXED, and the unit number to
127.
YJ3,502,mv2000,FIXED,127

YP

Sets basic Modbus client

settings

Syntax

YP p1,p2<terminator>

p1 Read cycle (125MS, 250MS, 500MS, 1S,

2S, 5S, 10S)

p2 Retry interval (OFF, 10S, 20S, 30S,1MIN,

2MIN, 5MIN, 10MIN, 20MIN, 30MIN, 1H)

Query

YP?

Example Set the read cycle to 500 ms and the retry

(reconnection) interval to 10 minutes.
YP500MS,10MIN

YR

Sets a Modbus client

transmission command

Syntax

YR p1,p2,p3···<terminator>

p1 Command number (1 to 16)
p2 Command type (OFF, R, R-M, W, W-M)

Description Parameters p3 and subsequent parameters vary

depending on the p2 setting as follows:

If p2 is OFF

There are no parameters after p2.

If p2 is R [read into external input channels]

p3 First channel (external input channel

number)

p4 Last channel (external input channel

number)

p5 Server number (1 to 16)
p6 First register number (30001 to 39999,

40001 to 49999, 300001 to 365536, 400001
to 465536)

p7 Register data type (INT16, UINT16,

INT32_B, INT32_L, UINT32_B, UINT32_L)

4.6 Basic Setting Commands