4-25

Commands

IM MV1000-17E

1

2

3

4

5

6

7

App

Index

Example Enable the automatic display switching, switch

to the group display, set the scale display to ON,
and set the digital display to OFF.
UD4,ON,GROUP,ON,OFF

Description • Parameter p2 is valid for the trend, digital, or

bar graph displays. Use the TP command to
set the scroll interval.

• Parameters p3 to p7 are valid for the trend

display.

PS

Starts/stops measurements

Syntax

PS p1<terminator>
p1 Measurement start/stop

0

Start

1

Stop

Example Start measurement.

PS0

Description When the MV starts measuring, it records the

display, event, and report data to the internal
memory.

AK

Releases the alarm output (alarm

acknowledge)

Syntax

AK p1<terminator>
p1 Alarm acknowledge execution (0)

Example Release the alarm output (execute alarm

acknowledge).
AK0

EV

Executes manual sample,

manual trigger, snapshot, or

forced timeout

Syntax

EV p1<terminator>
p1 Operation type

0

Execute manual sampling.

1

Activate a manual trigger.

2

Take a snapshot.

3

Expire the display data timer.

4

Expire the even data timer.

Example Execute manual sampling.

EV0

Description EV1 is valid only when the key trigger is set

to ON with the TE command (sets sampling
conditions of the event data). It functions the
same as the key trigger.

CL

Executes manual SNTP

Syntax

CL p1<terminator>
p1 Manual SNTP execution (0)

Example Synchronize the clock manually.

CL0

CV

Switches the trend interval

Syntax

CV p1<terminator>
p1 Display rate (0, 1)

0

Switch to the primary trend interval
(standard rate)

1

Switch to the secondary trend
interval

Example Change the trend interval to the secondary trend

interval.
CV1

MS

Writes a message (displays and

writes)

Syntax

MS p1,p2,p3<terminator>
p1 Message number (1 to 100)
p2 Destination where messages will be written

GROUP Specify a single group
ALL

All groups

p3 Group number

Example Write the message number 8 message to group

1.
MS8,GROUP,1

Description • This command displays the message to the

screen and writes the message in the display
data and event data.

• If you omit p2, the message is written to all

groups.

BJ

Writes a free message

Syntax

BJ p1,p2,p3,p4<terminator>
p1 Message number (1 to 10)
p2 Message (up to 32 characters)
p3 Destination type where messages will be

written
GROUP Specify a single group
ALL

All groups

p4 Destination where messages will be written

If p3 is set to

GROUP Group number

Example Use message number 3 and write the word

“ALARM” to all groups.BJ3,ALARM,ALL

Description If you omit p3, the message is written to all

groups.

EJ

Changes the login password

Syntax

EJ p1,p2,p3<terminator>
p1 Old password (up to eight alphanumeric

characters)

p2 New password (up to eight alphanumeric

characters)

p3 New password (up to eight alphanumeric

characters)

Example Change the old password “PASS001” to the new

password “WORD005.”
EJPASS001,WORD005,WORD005