Tu sets an event action, Sk sets a computation constant – Yokogawa Button Operated MV2000 User Manual

Page 92

Advertising
background image

4-18

4.4 Setting Commands (Setting)

IM MV1000-17E

If p2 is set to WEEK (day of week/time designation)

Syntax

TK p1,p2,p3,p4,p5<terminator>
p1 Timer number (1 to 4)
p2 Timer designation (WEEK)
p3 Designation of the day of the week (SUN,

MON, TUE, WED, THU, FRI, SAT)

p4 Time (hh:mm) (00:00 to 23:59)
p5 Timer operation (SINGLE, REPEAT)

If p2 is set to MONTH (day/time designation)

Syntax

TK p1,p2,p3,p4,p5<terminator>
p1 Timer number (1 to 4)
p2 Timer designation (MONTH)
p3 Day (1 to 28)
p4 Time (hh:mm) (00:00 to 23:59)
p5 Timer operation (SINGLE, REPEAT)

If p2 is set to YEAR (month/day/time designation)

Syntax

TK p1,p2,p3,p4,p5,p6<terminator>
p1 Timer number (1 to 4)
p2 Timer designation (YEAR)
p3 Month designation (JAN, FEB, MAR, APR,

MAY, JUN, JUL, AUG, SEP, OCT, NOV,
DEC)

p4 Day designation (1 to 31) The selectable

range varies on the specified month.

P5 Time (hh:mm) (00:00 to 23:59)
p6 Timer operation (SINGLE, REPEAT)

Example Specify 8:30 on April 28 every year for timer

number 3.
TK3,APR,28,08:30,REPEAT

Query

TK[ p1]?

Example Specify hour 21 every Thursday for timer number

2.
TK2,WEEK,THU,21:00,REPEAT

TU

Sets an event action

Syntax

TU p1,p2,p3,p4,p5,p6,p7<terminator>
p1 Logic number (1 to 40)
p2 Event type

NONE
REMOTE

Remote control

RELAY

Alarm output relay

SWITCH

Internal switch

ALARM

Alarm occurrence

TIMER

Timer expiry

MATCHTIMETIMER

Match time expiry

USERKEY

USER key

p3 Event detail

p2

=REMOTE

Remote number (1 to
8)

p2

=RELAY

Relay number

p2

=SWITCH

Internal switch
number

p2

=TIMER

Timer number (1 to 4)

p2

=MATCHTIMETIMER Match timer number

(1 to 4)

p2

=Other

Space

p4 Action type

MEMORYSTART/STOP Start/stop sampling
MEMORYSTART

Start sampling

MEMORYSTOP

Stop sampling

TRIGGER

Event trigger

ALARMACK

Alarm acknowledge

MATHSTART/STOP Start/stop computation
MATHSTART

Start computation

MATHSTOP

Stop computation

MATHRESET

Reset computation

SAVEDISPLAY

Save display data to
an external storage
medium

SAVEEVENT

Save event data to an
external storage medium

MESSAGE

Write a message

SNAPSHOT

Take a snapshot

MANUALSAMPLE

Execute manual

sampling

TIMERRESET

Reset the relative timer

DISPLAYRATE1/2 Switch the trend

interval

DISPLAYGROUPCHANGE Switch the display group
FLAG

Raise a flag

TIMEADJUST

Synchronize the clock

PANELLOAD

Load settings

p5 Event detail 2

p4

=TIMERRESET Timer number (1 to 4)

p4

=DISPLAYGROUPCHANGE Group number

p4

=FLAG

Flag number (1 to 8)

p4

=MESSAGE

Message number (1 to

100)

p4

=PANELLOAD Setup file number (1 to

3)

p6 Event detail 3

p4

=MESSAGE

Method of specifying

the destination where
messages are written

ALL

All display groups

SELECT

A specified display

group

p7 Event detail 4

If p6 is set to

SELECT Group number

Some p4 parameters (action type) are not
selectable depending on p2 (event type).

Some p4 parameters (action type) are not
selectable depending on the settings or on the
installation of options.

Query

TU[ p1]?

Example Execute memory start with the remote control input

(terminal 1).
TUREMOTE,1,MEMORYSTART

Description Set parameter p3 (relay number, internal switch)

according to the table in section 4.3.

SK

Sets a computation constant

Syntax

SK p1,p2<terminator>
p1 Constants number

Advertising