Specified Data Type and Write Operation
The MV writes the measured values of measurement channels according to the

specified data type as follows:

Specified Type

Measured Value

Value Written

INT16

Writes all values directly.

FLOAT_L

FLOAT_B

+Over

*

7f800000H(+∞)

-Over

*

ff800000H(-∞)

Skip

*

ff800002H(Nan)

Error

*

ff800004H(Nan)

Undefined data

*

ff800005H(Nan)

Burnout(Up)

*

7f800006H(Nan)

Burnout(Down)

*

ff800006H(Nan)

Other values

Writes the value including the decimal

place in FLOAT data type.

* For details on values, see section 5.3, “Binary Data Output Format.”

• Writing Computed Values of Computation Channels

• The computation function is an option (/M1 or /PM1).
• Writes computed values of computation channels to server registers.
• The data type of computed values is 32-bit signed integer.

W-M

40001 to 49999

400001 to 465536

INT 16, UINT 16,

INT 32_B, INT 32_L,

FLOAT_B, FLOAT_L

Computation channel

Number: 101 to 124 (MV1000)

101 to 160 (MV2000)

Data type: 32-bit signed integer

Register

Server

Data type

Access

method

MV1000 and MV2000

Write

Specified Data Type and Write Operation
The MV writes the computed values of computation channels according to the

specified data type as follows:

Specified Type

Computed Value

Value Written

INT16

Less than –32768

–32768

Greater than 32767

32767

+Over

*

32767

-Over

*

Skip

*

Error

*

–32768

Other values

Writes the value in INT16 data format.

UINT16

Less than 0

0

Greater than 65535

65535

+Over

*

65535

-Over

*

Skip

*

Error

*

0

Other values

Writes the value in UINT16 data

format.

INT32_L

INT32_B

Writes all values directly.

FLOAT_L

FLOAT_B

+Over

*

7f800000H(+∞)

-Over

*

ff800000H(-∞)

Skip

*

ff800002H(Nan)

Error

*

ff800004H(Nan)

Other values

Writes the value including the decimal

place in FLOAT data type.

* For details on values, see section 5.3, “Binary Data Output Format.”

7.3 Modbus Protocol Specifications