4.4 Setting Commands (Setting)

IM MV1000-17E

p3 Message display direction

HORIZONTAL
VERTICAL

p4 Scale display digits

NORMAL

3-digit display

FINE

4-digit display

p5 Current value display

MARK

Display using a mark

BARGRAPH

Display using a bar
graph

Query

TT?

Example Set the waveform to horizontal display and the

message direction to vertical, and display the
waveform by clearing the existing waveform at
memory start.
TTHORIZONTAL,ON,VERTICAL

SE

Sets the trend graph line width

and the number of grids

Syntax

SE p1,p2<terminator>
p1 Trend line width (1 to 3) [dot]
p2 Number of grids (4 to 12, AUTO)

Query

SE?

Example Set the trend waveform line width to 1 dot and

the number of grids to 10.
SE1,10

TB

Sets the bar graph display

Syntax

TB p1<terminator>
p1 Bar graph display direction

HORIZONTAL
VERTICAL

Query

TB?

Example Display the bar graph horizontally.

TBHORIZONTAL

SB

Sets the bar graph of a channel

Syntax

SB p1,p2,p3<terminator>
p1 Measurement, computation, or external

input channel number

p2 Base position of the bar graph display

NORMAL Normal (lower limit)
CENTER
LOWER Lower limit
UPPER Upper limit

p3 Number of scale divisions (4 to 12)

Query

SB[ p1]?

Example Set the number of scale divisions of the channel

002 bar graph to 5, and display the bar graph
from the span lower limit (scale lower limit if
scaling is enabled).
SB002,NORMAL,5

Description You can specify a computation channel (or make

a query) on models with the /M1 math option.
You can specify an external input channel (or

make a query) on models with the /MC1 external
input channel option.

TN

Sets the scale

Syntax

TN p1,p2,p3<terminator>
p1 Measurement, computation, or external

input channel number

p2 Display position (OFF, 1 to 10)
p3 Number of divisions (4 to 12, C10)

Query

TN[ p1]?

Example Set the channel 003 scale position to 2 and the

number of divisions to 10.
TN003,2,10

SV

Sets the moving average of a

measurement channel

Syntax

SV p1,p2,p3<terminator>
p1 Measurement channel number
p2 Moving average ON/OFF
p3 Number of samples for computing the

moving average (2 to 400) [times]

Query

SV[ p1]?

Example Set the number of samples for computing the

moving average on channel 002 to 12.
SV002,12

SC

Sets a channel display color

Syntax

SC p1,p2<terminator>
p1 Measurement, computation, or external

input channel number

p2 Display color (see SL (sets a trip line))

Query

SC[ p1]?

Example Set the channel 002 display color to blue.

SC002,BLUE

Description You can specify a computation channel (or make

a query) on models with the /M1 math option.
You can specify an external input channel (or
make a query) on models with the /MC1 external
input channel option.

TA

Sets an alarm point mark

Syntax

TA p1,p2,p3,p4,p5,p6,p7<terminator>
p1 Measurement, computation, or external

input channel number

p2 Mark type

ALARM Alarm mark
FIXED Fixed mark

p3 Scale board display ON/OFF
p4 Alarm level 1 color (see SL (sets a trip line))
p5 Alarm level 2 color (see SL (sets a trip line))
p6 Alarm level 3 color (see SL (sets a trip line))
p7 Alarm level 4 color (see SL (sets a trip line))

Query

TA[ p1]?

Example Display alarm marks on the channel 004 scale.

TA004,ALARM,ON