App index, Xt sets the temperature unit, Rf sets the key lock function – Yokogawa Button Operated MV2000 User Manual

Page 105: Rn sets basic login settings, Rp sets login and user limitations, Ro sets report types and generation times

Advertising
background image

4-31

Commands

IM MV1000-17E

1

2

3

4

5

6

7

App

Index

XM

Sets the memory sample

condition

Syntax

XM p1<terminator>
p1 Data type

DISPLAY Display data
EVENT Event data
E+D

Display data and event data

Query

XM?

Example Set the memory sampling condition to display

data.
XMDISPLAY

XT

Sets the temperature unit

Syntax

XT p1<terminator>
p1 Temperature unit (C, F)

Query

XT?

Example Set the temperature unit to Celsius.

XTC

RF

Sets the key lock function

p1=KEY

Syntax

RF p1,p2,p3,p4,p5,p6,p7<terminator>
p1 Type (KEY)
p2 START/STOP key (FREE, LOCK)
p3 HISTORY key (FREE, LOCK)
p4 MENU key (FREE, LOCK)
p5 USER key (FREE, LOCK)
p6 DISP/ENTER key (FREE, LOCK)
p7 T/DIV key (FREE, LOCK)

p1=FUNC (function keys)

Syntax

RF p1,p2,p3,p4,p5,p6,p7,p8
<terminator>
p1 Type (FUNC)
p2 Alarm acknowledge (FREE, LOCK)
p3 Message/batch (FREE, LOCK)
p4 Math (FREE, LOCK)
p5 Data save (FREE, LOCK)
p6 E-mail/FTP (FREE, LOCK)
p7 Time set (FREE, LOCK)
p8 Display function (FREE, LOCK)

p1=MEDIA (external storage media)

Syntax

RF p1,p2,p3<terminator>
p1 Type (MEDIA)
p2 External storage media operation (FREE,

LOCK)

p3 Load setup (FREE, LOCK)

Query

RF[ p1]?

Example Lock the MENU key (leave other keys unlocked).

RFKEY,FREE,FREE,LOCK,FREE,FREE,FREE

RN

Sets basic login settings

Syntax

RN p1,p2<terminator>
p1 Auto logout (OFF, 1MIN, 2MIN, 5MIN,

10MIN)

p2 Operation when logged out

OFF

Disable the MV operation

DISPLAY Allow only display-related

operations

Query

RN?

Example Set the auto logout time to 1 minute, and disable

the MV operation when logged out.
RN1MIN,OFF

RP

Sets login and user limitations

Syntax

RP p1,p2,···<terminator>
p1 User limit number (1 to 10)
p2 User limit item (KEY, FUNC, MEDIA)

Description Parameters p3 and subsequent parameters vary

depending on the p2 setting as follows:

p2=KEY

p3 START/STOP key (FREE, LOCK)
p4 HISTORY key (FREE, LOCK)
p5 MENU key (FREE, LOCK)
p6 USER key (FREE, LOCK)
p7 DISP/ENTER key (FREE, LOCK)
p8 T/DIV key (FREE, LOCK)

p2=FUNC (function keys)

p3 Alarm acknowledge (FREE, LOCK)
p4 Message/batch (FREE, LOCK)
p5 Math (FREE, LOCK)
p6 Data save (FREE, LOCK)
p7 E-mail/FTP (FREE, LOCK)
p8 Time set (FREE, LOCK)
p9 Display function (FREE, LOCK)

Query

RP[ p1,[ p2]]?

Example Lock the START, HISTORY, and DISP/ENTER

keys.
RP1,KEY,LOCK,LOCK,,,LOCK

p2=MEDIA (external storage media)

Syntax

RP p1,p2,p3<terminator>
p2 User limit item (MEDIA)
p3 External storage media operation (FREE,

LOCK)

p4 Load setup (FREE, LOCK)

Query

RP[p1]?

Example Limit access to the external storage medium and

the loading of setup data.
RPMEDIA,LOCK,LOCK

Description If key lock is enabled, setup data cannot be

loaded. You can place limitations on the loading
of setup data for users that are logged in.

RO

Sets report types and generation

times

To specify no report types

Syntax

RO p1<terminator>
p1 Report type (OFF)

Query

RO?

4.6 Basic Setting Commands

Advertising