Bh sets a batch text field, Eh sets a calibration correction, Bd sets an alarm delay – Yokogawa Button Operated MV2000 User Manual

Page 94: Sm sets the custom menu

Advertising
background image

4-20

4.4 Setting Commands (Setting)

IM MV1000-17E

intervals after the power is turned ON and
transmits the data when a FF command is
received. The previous output position is
held for each connection. Upon receiving
an FF command, the MV transmits the next
data and updates the output position. This
scheme compensates for the differences in
the processing power of the measurement PC
and the communication delay. This enables
data to be retrieved without dropouts if the
measurement PC reads the data before the
ring buffer is overwritten. For the output flow
diagram of FIFO data, see appendix 5.

BH

Sets a batch text field

Syntax

BH p1,p2,p3,p4<terminator>
p1 1
p2 Field number (1 to 8)
p3 Field title (up to 20 characters)
p4 Field characters (up to 30 characters)Field

title (up to 30 characters)

Query

BH[ p1,[ p2]]?

Example Set the title to “OPERATOR” and the text to

“DAQSTATION” for field number 2.
BH1,2,OPERATOR,DAQSTATION

Description For the characters that can be used, see

appendix 1.

EH

Sets a calibration correction

If p2 is set to BEGIN

Syntax

EH p1,p2,p3<terminator>
p1 Measurement channel number
p2 Type of operation (BEGIN)
p3 Number of break points in the calibration

segment (OFF, 2 to 16)
OFF

Calibration OFF

2 to 16 Number of break points

If p2 is set to SET

Syntax

EH p1,p2,p3,p4,p5<terminator>
p1 Measurement channel number
p2 Type of operation (SET)
p3 Break point designation (1 to 16)
p4 True value of the specified break point
p5 Measured value of the specified break

point

Description • Set parameter p1 according to the table in

section 4.3.

• The selectable range of p4 and p5 varies

depending on the current set range.

• If set to scale range, the selectable range of

p4 and p5 is –30000 to 30000.

• Set true value p4 so that the value increases

as break point p3 increases.

If p2 is set to END

Syntax

EH p1,p2<terminator>
p1 Measurement channel number
p2 Type of operation (END)

Example Example in which three break points are

specified on CH2
EH002,BEGIN,3
EH002,SET,1,0,1
EH002,SET,2,50,49
EH002,SET,3,100,101
EH002,END

Description • First, execute this command with the type of

operation set to BEGIN to specify the number
of break points.

• Set the values for the specified number of the

break points using the SET operation.

• Execute this command with the type of

operation set to END to finalize the settings.

• The EH2? command transmits the CH2

settings.

• The output example is as shown in the

example above.

• You cannot execute this command while the

MV is computing.

BD

Sets an alarm delay

Syntax

BD p1,p2<terminator>
p1 Measurement, computation, or external

input channel number

p2 Alarm delay (1 to 3600) [s]

Query

BD[ p1]?

Example Set the channel 001 alarm delay to 120 s.

BD001,120

Description Set parameter p1 according to the table in

section 4.3.

SM

Sets the custom menu

To set the main menu

Syntax

SM p1,p2,p3,p4,p5,p6,p7,p8,p9
<terminator>
p1

Type (DISP_MAIN)

p2 to p9 Menu items to be displayed

The menu items are displayed in the
specified order.

Only the specified menu items are
displayed.
TREND
DIGITAL
BAR
OVERVIEW
INFORMATION
TRENDHISTORY
LOG
4PANEL
ESC
EXPAND
SEPARATOR