Wr sets the instrument information output, Xe activates basic setting mode, Ye activates basic setting mode (cold reset) – Yokogawa Button Operated MV2000 User Manual

Page 112

Advertising
background image

4-38

IM MV1000-17E

Description • You can execute this command on models

with the /C2 or /C3 serial interface option.

• You can use this command when the serial

interface protocol is set to Master. For serial
interface settings, see section 2.3.

• The settings specified with this command take

effect when you save the settings with the XE
command and power-cycle the MV.

To set a command for writing floating type data

into Modbus registers

Syntax

YM p1,p2,p3,p4,p5,p6,p7<terminator>

p1 Command number (1 to 16)
p2 Command type

W

Write data from measurement

channels

W-M

Write data from computation

channels

p3 First channel number

Measurement channel number (1 to 48) if

p2 is set to W

Computation channel number (101 to 124)

if p2 is set to W-M

p4 Last channel number (1 to 48)

Measurement channel number (1 to 48) if

p2 is set to W

Computation channel number (101 to 124)

if p2 is set to W-M

p5 Server number (1 to 16)
p6 First register number (40001 to 499991,

400001 to 465536)

p7 Register data type

INT16 16-bit signed integer
UNIT16 16-bit unsigned integer
INT32_B

32-bit signed integer (Big

Endian)

INT32_L

32-bit signed integer (Little

Endian)

FLOAT_B

32-bit floating point (Big

Endian)

FLOAT_L

32-bit floating point (Little

Endian)

Example Using command number 1, write the data from

measurement channels 1 to 16 to the registers
at server number 3 starting from register
number 40001 in 32-bit floating point format (Big
Endian).
YM1,W,1,16,3,40001,FLOAT_B

Query

YM?

Description The selectable range of the first channel number

(p3) and last channel number (p4) varies
depending on the model.

WR

Sets the instrument information

output

Syntax

WR p1,p2,p3,p4<terminator>

p1 Memory/Media state ON/OFF
p2 Self diagnosis ON/OFF
p3 Communication error ON/OFF

p4 Memory stop ON/OFF

Query

WR?

Example Output various information.

WRON,ON,ON,ON

XE

Activates Basic Setting Mode

Syntax

XE p1<terminator>
p1 Store or discard the settings (STORE,

ABORT)

Example Save the setup data of the basic setting

commands.
XESTORE

Description To activate the settings that are changed with

the basic setting commands, you must save the
settings with the XE command. Make sure to
save the settings with the XE command before
changing from Basic Setting Mode to Operation
Mode. Otherwise, new settings will not take
effect.

YE

Activates Basic Setting Mode

(cold reset)

Syntax

YE p1<terminator>
p1 Setting activation

STORE Start by saving the basic settings
ABORT Start without saving basic settings

Example Start by saving the basic settings.

YESTORE

4.6 Basic Setting Commands