Command Connection to WMT703

In order to troubleshoot or reconfigure WMT703, you may need to open
a command connection to the sensor as follows:

1.

Start AWS Client software.

2.

From the AWS Client menu, select Settings - Options.

3.

Create two new function key mappings as shown in Figure 124
below.
- $0OPEN<CR><LF>
- <CR><LF>

1101-040

Figure 124 Defining Function Key Mappings for WMT703

4.

Connect to QML201 logger as described in section Opening
Service Connection on page 150.

5.

Open command connection on QML201 by typing open<CR> to
the AWS Client terminal window.

6. Type

command

open COM1<CR>. This should output a response

Terminal I/O re-routed to COM1

.

7.

Press F11 (or other function key where the open command was
programmed to in step 3 above) to send the open command to
WMT703.