Set Point (SP) Output Signal Connections

Set Point (SP) output signal connection is required only if TIO is mated to the
flow controller and will be used as a source for a Set Point control signal.
Depending on the jumper J2 configuration, SP output signal can be set to 0-5,
0-10 Vdc or 4-20 mA.

Table 4.1 Maximum rated values for PV input signals

PV

INPUT

TYPE

J2 JUMPER

CONFIGURATION

MAXIMUM

SIGNAL

LEVEL

NOTE

J2D

J2E

J2F

0-5 Vdc

10 -11

14 -15

17-18

≤6 Vdc

5-10 Vdc

11 -12

14 -15

17-18

≤11 Vdc

+5Vdc reference signal
must be used (GFM/GFC option)

0-10 Vdc

11 -12

14 -15

17-18

≤11 Vdc

Special Order option! (PCB
hardware must be changed)

4-20 mA

10 -11

13 -14

16-17

≤25 mA

(249 Ohm passive, not isolated
current input)

3

2

1

6

5

4

9

8

7

12

11

10

15

14

13

18

17

16

21

20

19

A

B

C

D

E

F

G

Figure 4.2 - TIO Input/Output Configuration Jumpers

PV input (+) --------------- pin 4 of the 9 pin “D” connector.
PV input (-) --------------- pin 8 of the 9 pin “D” connector.