91

UART ERROR CODES

1

Not Supported Command or Back Door is not enabled.

2

Wrong # of Arguments.

3

Address is Out of Range (MR or MW commands).

4

Wrong # of the characters in the Argument.

5

Attempt to Alter Write Protected Area in the EEPROM.

6

Proper Command or Argument is not found.

7

Wrong value of the Argument.

8

Reserved.

9

Manufacture specific info EE KEY (wrong key or key is disabled).

DIAGNOSTIC AND SYSTEM EVENTS CODES AND BIT POSITION

Code

Event Description

Bit position

0

CPU Temp. High

0x0001

1

High Flow Alarm

0x0002

2

Low Flow Alarm

0x0004

3

Range between H-L

0x0008

4

Tot#1 > Limit

0x0010

5

Tot#2 > Limit

0x0020

6

OptPulse Queue

0x0040

7

Flow OverLimit

0x0080

8

Vcc OutOfRange

0x0100

9

SerComm. ERROR

0x0200

A

EEPROM ERROR

0x0400

B

Power on Event

0x0800

C

Password Event

0x1000

D

Fatal Error

0x2000

INTERNAL K-FACTOR TABLE LIST

Index

Gas

K-Factor

1

Ar

1.4573

2

AsH3

0.6735

3

BF3

0.5082

4

Br2

0.8083

5

C2H2

0.5829

6

C2N2

0.6100

7

CH4

0.7175

8

Cl2

0.8600

9

CO2

0.7382

10

COF2

0.5428

11

COS

0.6606

12

CS2

0.6026

13

F2

0.9784

14

H2

1.0106

15

He

1.4540

16

N2O

0.7128

17

NH3

0.7310

18

NE

1.4600

19

NO

0.9900

20

O2

0.9926

21

SO2

0.6900

22

Xe

1.4400