Aalborg TIO Totalizer I/O Flow Monitor/Controller User Manual
Page 81
78
AALBORG
7
TOT
A
LIZER-IO ASCII SOFTW
ARE INTERF
ACE COMMANDS
N
OTE
:
A
N
"*"
INDICA
TES
POWER
U
P
D
EF
AUL
T
SETTINGS
.
A
N
"**"
INDICA
TES
OPTIONAL
FEA
TURE
NOT
A
V
A
ILABLE
O
N
A
LL
MODELS
.
COMMAND
NAME
DESCRIPTION
NO.
COMMAND SYNT
A
X
COMMAND
ARGUMENT 1
ARGUMENT 2
ARGUMENT 3
ARGUMENT 4
RESPONSE
Flow
Requests the current flow
reading in current EU
1
F
<V
alue> (Actual flow in
current engineering units)
Set Point
Set point value in current EU
(Read, Write) With Argument
#2 = ‘S’ set point value will be
saved in the EEPROM
2
S
NO ARGUMENT
(read status)
S:<V
alue> (Set Point in
current engineering units)
Example: S:20.5
<V
alue> (write,
not saved in EEP-
ROM memor
y)
S:<V
alue> (Set Point in
current engineering units)
Example: S:20.5
<V
alue>(write,
saved in EEPROM
memor
y)
S
S:<V
alue> ,S (Set Point in
current engineering units)
Example: S:20.5,S
Density
Read / Set Fluid Density for
standard conditions in g/litr
[0.000001-10000.0] g/litr
3
D
NO ARGUMENT
(read current
value)
D:<V
alue> (Actual density
in g/litr)
Example: D:1.25
<V
alue>
(write and save
new value)
D:<V
alue> (Actual density
in g/litr)
Example: D:1.56
Diagnostic
Events
Register
Read/Reset current status of
Diagnostic Events Register
See list of the Diagnostic
Events below
.
4
DE
NO ARGUMENT
(read status)
DE:0x10 0x10 – diagnostic
word (16 bits wide)
R (reset Event
Log register to
0x0000)
DE:0x0