c) Input/Output Jumper Configuration

NOTE: Your TIO device input / output jumpers were configured at the
factory according to your order. There is no need to change the input
/ output jumper’s configuration unless different input is being used.
Before applying power and process signals make sure the input /
output jumpers are installed in the correct position (See Table 6.4).

,

TABLE 6.4 J2 INPUT / OUTPUT JUMPER CONFIGURATION OPTIONS FOR GFC SERIES

FLOW CONTROLLERS

TIO PV TYPE

J2 JUMPER CONFIGURATION

GFC

CABLE KIT

NOTE

OUTPUT INPUT

J2A

J2B

J2C

J2D

J2E

J2F

0-5Vdc 0-5Vdc 2 - 3

5 - 6

8 - 9

10-11 14-15 17-18

KIT-TC-

XXXXX-XX

Supported by

all GFC Kits,

except

KIT-TC

0-5Vdc

4-20

mA

2 - 3

5 - 6

8 - 9

10-11 13-14 16-17

N/A (user

custom

cable

assembly

only)

Not supported

by GFC Cable

Kits

4 – 20

mA

0-5Vdc 1 - 2

4 - 5

7 - 8

10-11 14-15 17-18

N/A (user

custom

cable

assembly

only)

Not supported

by GFC Cable

Kits

4 – 20

mA

4 – 20

mA

1 - 2

4 - 5

7 - 8

10-11 13-14 16-17

N/A (user

custom

cable

assembly

only)

Not supported

by GFC Cable

Kits

0 - 10

Vdc

0 - 10

Vdc

2 - 3

5 - 6

8 - 9

11-12 14-15 17-18

NOT

SUPPORTED

BY GFC

Special Order

option! (PCB

hardware

must be

changed)