Iii. options & accessories, Optional second alarm/control module – Myron L 729II User Manual

Page 23

Advertising
background image

III. OPTIONS &

ACCESSORIES

A.

SC/SCO MODULE

(SECOND ALARM/CONTROL OPTION)

(Digital & OEM Models ONLY)

-SC

Second Alarm Control Module ordered with

Monitor/controller.

SCO

Second Alarm Control Module Kit ordered separately.

1. DESCRIPTION:

An essential component for applications requiring a DUAL

setpoint. The Second Alarm/control module allows the user

additional flexibility by being able to sound TWO Alarms, and

Control TWO functions with the second 10 amp relay.

The set points are non-overlapping. The #2 alarm/control (HIGH

set point) rides on top of the #1 alarm/control (LOW set point).

SCO kit comes with all items necessary to install and operate: SC

Module, front panel harness with LED, switch, bezel, cap and two

O-rings (006 & 008); and replacement lower front panel label

(L2ALARM).

Specifications:

Control Function:

Setpoint control continuously adjustable 0-100% of span

Hysteresis:

Adjustable from 0.3-3% of full scale

Indicators:

Above (red) and below (green) setpoint LEDs (reversible)

Relay Contact Rating:

SPDT 10 amp ~ 250 VAC, 30 VDC. Relay operates

increasing or decreasing reading (selectable)

Solid State Output:

Powered — 24VDC 30mA Maximum

2. INSTALLATION:

Briefly -

The Second Alarm/control module plugs into the main

Monitor/controller circuit board.

The LED/switch harness is installed into the front panel.

Set point and hysteresis are set per “your“

requirements.

If this option is installed, skip to III.A.2.a.

WARNING: BEFORE STARTING, IF MONITOR/

CONTROLLER IS INSTALLED, ENSURE THE POWER

IS OFF. FAILURE TO DO SO COULD CAUSE DAMAGE

TO THE INSTRUMENT, AND COULD BE HARMFUL OR

FATAL

TO

PERSONNEL.

ONLY

QUALIFIED

PERSONNEL

SHOULD

INSTALL

OR

SERVICE

ELECTRICAL EQUIPMENT.

Physical

If the front panel has all ready been removed from the enclosure

skip to #3.

MAIN Circuit Board

1. Using a standard slot screwdriver remove the

screws on the front panel.

2. Carefully wiggle the front panel to loosen the gasket and

pull gently toward you. Do not pull more than

about 8 inches/20CM or you could damage the wiring

harness.

3. Turn the front panel around so that the back side is facing

you and set aside for now.

4. Remove BLACK JUMPER from MAIN Circuit Board

connector located next to the transformer as shown in

figure III.A.2.

NOTE: Do not lose BLACK JUMPER. It must be reinstalled if

second relay is removed for any reason and the #1 relay

is expected to operate.

5. Carefully press the SCO Second Alarm/Control Module

into MAIN Circuit Board as shown in figure III.A.4.

When fully seated the SCO Module will snap into place.

6. Connect the Solid State output to PA or user supplied

24VDC/30mA alarm/valve or ??, and/or control wires

to relay #2, as required, see figure III.A.4*.

a. Place the control cable and user supplied

watertight cable restraint into the enclosure’s

appropriate access hole.

b. Neatly connect the control wires to the

Monitor/controller’s appropriate connectors. See

figure III.A.4.

*CAUTION: The relay connectors require only a small

screwdriver or a pen to push on the release levers. The release

levers may be broken or damaged if not pushed straight. DO NOT

push the release levers sideways.

19

!

CAUTION - READ FOLLOWING CAREFULLY

OPTIONAL SECOND ALARM/CONTROL MODULE

SPC

INC

PA

LED/SWITCH

HARNESS

RUBBER TAPE

(DO NOT REMOVE -

MUST BE IN PLACE

TO PREVENT SHORT)

SET POINT #2

CONVERSION

SET POINT #2

HYSTERESIS

SET POINT #2 (high)

ADJUST

COM

RELAY #2

}

NO

NC

SOLID STATE OUTPUT (24VDC 30mA)

PA™ PIEZO ELECTRIC ALARM OR

RA™ REMOTE ALARM OR

CUSTOMER CONNECTION

Figure III.A.1

CM

NO NC