Myron L 729II User Manual

Page 27

Advertising
background image

B.

4A/4AO MODULE (4-20mA OPTION)

Available only on the digital models 728II, 729II, 723II and

724II, or analog and digital OEM.

-4A

4-20mA Self/Remote-powered Isolated output module

ordered with Monitor/controller.

4AO

4-20mA Self/Remote-powered Isolated output module

ordered separately (includes harness).

1. DESCRIPTION

The 4-20mA option gives the Series II Monitor/controller the

ability to send a signal very long distances with minimal

interferences and signal degradation. The output is an Isolated 4-

20mA signal that corresponds to the full scale range of the

Monitor/controller into which it is installed. This output is easily

configured to be either self-powered or remote-powered as

required for your particular application.

NOTE: The maximum impedance of the user’s current sensor

should not exceed 400 ohms.

Since the output is an isolated current loop, it is the ideal choice

for applications requiring; a control signal to be run very long

distances, systems requiring a 4-20mA input or in instances

where isolation is necessary.

As the output is isolated, and a current, it is useful for long

distance interface, especially where wiring resistances may be

high, and/or the ground potentials may differ between the sensor

input ground and the current receiving instruments ground.

The 4-20mA output will not be degraded in accuracy even when

the ground differences are as much as 120VAC @ 60Hz.

Interface wire resistance of 350Ω will not degrade the accuracy of

the output when interfaced to a typical 250Ω input impedance of a

transmitter current input device.

The output is capable of driving a minimum of 600Ω worst case,

therefore, will satisfy virtually all modern interface requirements.

Current input devices usually have an input impedance of 250Ω,

however, some older designs can have as high as 500Ω or as low

as 10Ω. This “-4A” option will drive any impedance from 0 to 600Ω

without any degradation of performance.

There are two modes in which current loop transmitters operate;

Self-Powered and Remote-Powered.

Self-Powered — the transmitter provides the power to drive

the 4 to 20 mA current. See figure III.B.1.

Remote-powered — the receiving instrument provides the

power to drive the 4 to 20 mA current. See figure III.B.2.

Specifications

Self-Powered and Remote-Powered

Drive Impedance — 0 to 600Ω

Common Mode Maximum — 120VAC @ 60 Hz

Isolation — 100pf max. to Model 750II circuit common

100pf max. to input power line

Calibration

Two multi-turn pots — Factory Set.

4mA = Zero (0)

20mA = Full Scale

Calibration is NOT required. However, if you feel you must verify

or recalibrate, see Recalibration below.

2. INSTALLATION

Briefly -

The 4-20 Module replaces the plastic display retainer plate

attached to the front panel.

The 4-20 Module harness is attached to the main circuit board as

marked ‘4-20’. See figure III.B.4.

The 4-20 output is wired as required - Self-powered or Remote-

powered. See figures III.B.1 & III.B.2.

WARNING: BEFORE STARTING, IF MONITOR/

CONTROLLER IS INSTALLED, ENSURE THE POWER

IS OFF. FAILURE TO DO SO COULD CAUSE DAMAGE

TO THE INSTRUMENT, AND COULD BE HARMFUL OR

23

Figure III.B.1

(+)

(-)

+

-

(+)

SIGNAL OUT

POWER OUT

+

Self - Powered

CURRENT INPUT INSTRUMENT

N

Figure III.B.2

(+)

(-)

+

-

(+)

SIGNAL OUT

POWER OUT

POWER IN

+

Remote - Powered

CURRENT INPUT INSTRUMENT

+ 35 VDC

MAXIMUM

N

POWER IN

SO

P

O

P

I

SO

P

O

P

I

!

CAUTION - READ FOLLOWING CAREFULLY