Iii. general warnings and cautions – Elkhart Brass Unibody Valve User Manual

Page 11

Advertising
background image

11

800.346.0250 • www.elkhartbrass.com

III. GENERAL WARNINGS AND CAUTIONS

• All personnel who may be expected to operate this equipment must be thoroughly trained in its safe

and proper use.

• Become thoroughly familiar with the hydraulic characteristics of this equipment.

• Always open and close valves slowly to avoid water hammer.

• After each use, and on a scheduled basis, inspect equipment per instructions in the maintenance

Section V.

• Keep fingers and hands clear of moving parts.

• Do not use lubrication on the valve ball or seats.

• Do not wrench on the valve body or the opposite adapters.

• Disconnect power before servicing an electric valve.

• Clear debris from waterway before the valve is installed.

• Foreign materials such as metal chips could jeopardize the sealing capability of the valve. Any drilled

holes required in the plumbing should be added, and the chips removed from the waterway, prior to

installation of the valve.

• Do not exceed rated operating pressure for any valve as listed in Table 1.

Table 1 – Pressure

Model

Rated Operating Pressure

C

v

Number

(psi)

Value

EB15

600

139

EB20

600

139

EB25

250

277

EB30

250

510

EB35

250

510

EB40

250

694

EB3B

250

340

EB4B

250

660

EB4J

285

400

EB5B

250

1080

EB5J

285

650

EB6B

250

1613

EB6D

250

1950

EB6J

285

1050

EB6S

275

1050

EB8B

250

3759

EB8J

285

2200

EB8S

275

2200

Butterfl

y

V

a

lv

e

s

Ball

V

a

lv

e

s

Important:

Before installing and operating this equipment, read and study this manual thoroughly. Proper

installation is essential to safe operation. In addition, the following points should be adhered to in order

to assure the safety of equipment and personnel.

NFPA 1901 Standards specify a minimum of 3 seconds is required to open or close a 3” or larger valve.

Advertising