XIV. PROGRAMMING (E3F, E4F, E5F, & E6F)

Programming of the E3F, E4F, E5F, and E6F actuators can be accomplished though the use of the J1939 Data

Bus, a UBEC controller, or any hard wired, external switches. Programming with the UBEC can be accomplished

through the use of the standard programming code found on Pages 53-61.
NOTE: The UICS2 controller can not be used with E3F, E4F, E5F, or E6F actuated valves.
Programming

Note: In order to control the E3F, E4F, E5F, and E6F actuators with a UBEC controller, the controller

must be programmed as a Remote unit. The ID number and model type for the UBEC controller

must match the ID number and model type of the E3F, E4F, E5F, or E6F actuator. Refer to the

Programming section on Pages 53-61.

Program Valve Polarity (E3F, E4F, E5F, or E6F SWITCHES ONLY)

1. Reverse the power and ground valve control pins on the 12-Pin connector on the actuator. This will result

in Pin 6 becoming the positive valve control and Pin 7 becoming the negative valve control. Refer to Wiring

section on Page 68.

2. Initiate the Automatic Valve Position Calibration routine. Upon completion of this routine, the valve should

be in the CLOSED position. Refer to Calibration section on Page 63.

Valve Configuration Transfers

The valve configuration transfer codes enable the user to transfer information from a remote unit (UBEC) to

an E3F, E4F, E5F, or E6F actuator or visa versa. The controller ID, valve type, and units of measure can all be

transferred using this function.

Note: The valve configuration transfer must be completed in order to change the above listed

options on the E3F, E4F, E5F, or E6F actuator.

Transfer Information From Remote Unit To E3F, E4F, E5F, or E6F (4110)

1. Enter code 4110

– Press OPEN button 4 times to enter 4

– Press CLOSE button to move the cursor to the next digit

– Press OPEN button 1 time to enter 1

– Press CLOSE button to move the cursor to the next digit

– Press OPEN button 1 time to enter 1

2. The pressure display will show 4110
3. After 3 seconds the pressure display will show CF_P
4. Press the OPEN button once to change the display to yes
5. Press the PRESET button and hold for 5 seconds to transfer the information
Transfer Information From E3F, E4F, E5F, or E6F To Remote Unit (4120)

1. Enter code 4120

– Press OPEN button 4 times to enter 4

– Press CLOSE button to move the cursor to the next digit

– Press OPEN button 1 time to enter 1

– Press CLOSE button to move the cursor to the next digit

– Press OPEN button 2 times to enter 2

2. The pressure display will show 4120
3. After 3 seconds the pressure display will show CF_r
4. Press the OPEN button once to change the display to yes
5. Press the PRESET button and hold for 5 seconds to transfer the information