CODE

DESCRIPTION

VALVE CURRENT

WARNING

12

No Sensor Signal

Voltage Out of Range

Normal

Less than 10 AMPS

2 LEDs Blink

13

No Sensor Signal

Voltage Out of Range

High

10 to 18 AMPS

2 LEDs Blink

14

No Sensor Signal

Voltage Out of Range

Stalled

Greater than 18 AMPS

2 LEDs Blink

15

Sensor Signal Does Not

Change

Normal

Less than 10 AMPS

2 LEDs Blink

16

Sensor Signal Does Not

Change

High

10 to 18 AMPS

2 LEDs Blink

17

Sensor Signal Does Not

Change

Stalled

Greater than 18 AMPS

2 LEDs Blink

18

Sensor Signal Good

High Current Sensed

High

10 to 18 AMPS

All LEDs Blink

Table 5. Diagnostics Codes

Error Code

Error codes will be shown in the digital displays.
F1

There is a valve calibration problem. After the valve is calibrated, the system checks that the voltage range is

within normal limits (0.2 to 4 volts).
F5

No pressure sensor is detected.
E202

An invalid program code has been entered. Re-enter program code when the digital display resets.
E204

There is no signal from the sensor. This code is only displayed when in a calibration mode. Troubleshoot the

sensor and the associated wiring.