E3f and e4f quick start instructions – Elkhart Brass Unibody Valve User Manual

Page 5

Advertising
background image

5

800.346.0250 • www.elkhartbrass.com

E3F AND E4F QUICK START INSTRUCTIONS

5. Wire Harness Diagram

6. Valve Position Calibration

(SEE PAGE 63 OF MANUAL.)

NOTE: The valve should be partially open before starting valve position calibration.

AUTOMATIC POSITION CALIBRATION

1. Press and hold the CLOSE and PRESET buttons for 5 seconds.

2. The valve will cycle through the CLOSED and OPEN positions and finish in the CLOSED position.

AUTOMATIC POSITION CALIBRATION (NO EXTERNAL INPUTS)

1. Supply a 12/24-VDC signal to Pin 5 on the 12-Pin connector.

2. The valve will cycle through the CLOSED and OPEN positions and finish in the CLOSED position.

Pressure – Not required unless pressure display is found to be inaccurate.

(See page 64)

Flow – Always required with UBEC3 controller.

(See page 64-65)

7. Common Error Codes

• F1 – Valve calibration problem.

See Valve Position Calibration above.

• F5 – No pressure sensor detected.

Check sensor harness connections.

(See page 70)

• E202 – Invalid program code entered.

See Pages 62 for programming codes.

• E204 – No signal from sensor.

Check harness connections.

(See page 70)

• OPEN and CLOSE LED Flashing – Position Calibration needed.

See Valve Position Calibration above.

NOTE: See page 66 of manual for more diagnostic information.

8. Special Notes

• EB6D Butterfly Valves

These valves utilize a high frictional coefficient seat material. This high friction value could result in a high torque

scenario when closing new, dry valves. In the event of a high torque scenario, there is a possibility of the

controller reaching its preset amperage limit, causing the controller LEDs to flash and reset the controller. Once reset,

the controller will function properly. For this reason it is recommended that repeatedly opening and closing of the

valve while dry is avoided.

Note: The above scenario is only possible in the absence of water on the valve seat.

• EBXJ Butterfly Valves

1. Press and hold the OPEN and CLOSE buttons for 5 seconds.

2. Enter code 2160

Press OPEN button 2 times to enter 2

Press CLOSE button to move the cursor to the next digit

Press OPEN button 1 time to enter 1

Press CLOSE button to move the cursor to the next digit

Press OPEN button 6 times to enter 6

Result: The PRESSURE display shows 2160.

3. After 3 seconds TYPE1 (standard) or TYPE2 (reverse) shows in the display.

4. Use the OPEN button to toggle between the two.

5. Press the PRESET/CAF SELECT button and hold for 5 seconds to exit and save the programmed parameters.

Input Device Options

12/24 VDC

Power Supply

Motor

Leads

J1939 Data Bus

UBEC Controller

Remote Inputs

Can Bus

Wire Not Supplied

External

Inputs

Wire Not

Suppplied