Primary control and display module, Program primary or remote (code 212), Remote control and display module – Elkhart Brass Unibody Valve User Manual

Page 54

Advertising
background image

54

ELKHART BRASS MANUFACTURING COMPANY, INC

Primary Control and Display Module

Primary displays are programmed with the module function PRIMARY. A primary display receives input

from the valve and pressure sensor. When it is programmed with ID 0 it will not output information on

to the datalink. When it is programmed with ID 1 to ID 99 it will provide information (via the datalink) to

remote displays.

Program Primary or Remote (Code 212)

Note: The red CLOSED LED must be flashing to change the program.

1. Use the OPEN button to set the first digit of code 212, two green LEDs on. Each time the OPEN button is

pressed the next green LED will go on.

Note: If an error is made when entering the code, continue to press the OPEN button until all 9

LEDs are on, press again and the LEDs will all be off, press to return to the first LED on.

2. Press the CLOSE button to move the cursor to the next digit. Now all LEDs will be off and ready for the

second digit to be entered. Press the OPEN button once, one green LED on.

3. Press the CLOSE button to move the cursor to the next digit. All LEDs will be off. Press the OPEN

button twice, two green LEDs on.

4. After 3 seconds, for Primary (Pri) all LEDs will be on.

For Remote (Slave) (SLA) alternate LEDs will be on.

Use the OPEN button to toggle between the Pri and SLA.
5. Press the PRESET button for 3 seconds to exit. All LEDs will go off to indicate the data is accepted and

the control module return to normal operation after 2 seconds.

6. All LEDs will flash if there is a problem when exiting the programming mode. Press any button to

cancel the warning or let time out after 10 seconds.

7. Power must be cycled for programming change to become effective.

Remote Control and Display Module

Remote displays are programmed with the module function REMOTE. A remote display must be programmed with

the same ID number as a primary display. It receives information for the display of valve position and

pressure from the primary display over the datalink. All program code features are programmed independently

of the primary display. No calibration is necessary on a remote display.

Advertising