Figure 44. Flow Sensor Location Guide

The preferred location for the mounting of a flow

sensor is on the top half of the pipe. The best

orientation is vertical. If the sensor is mounted on

the bottom of the pipe, it may be susceptible to the

accumulation of dirt.

When mounting the sensor after the pipe

diameter is reduced the length L must be

at least 2 times the pipe diameter.

When mounting the sensor after a

valve the length L must be at least 14

times the pipe diameter.

When mounting the sensor after an

elbow the length L must be at least

6 times the pipe diameter.

When mounting the sensor before a valve or

an elbow the length L must be at least equal

to the pipe diameter.

Before Valve or Elbow

L > 1 X PIPE DIA.

After Elbow

L > 6 X PIPE DIA.

After Valve

L > 14 X PIPE DIA.

After Reduction

L > 2 X PIPE DIA.

Best Orientation is

Vertical

L

L

L

L