XI. PROGRAMMING (UBEC1)

When in the program access mode the LEDs are used to set the control and display module to be

a primary or remote and to set the ID number. To gain access to the program features a three digit

program code must be entered.

Programming Mode

Note: The valve must be closed and the red CLOSED LED must be on to program the valve control.
Press and hold the CLOSE button then press and hold the OPEN button. After 5 seconds the red

CLOSED LED will flash. The program code can now be entered.

Program Valve Polarity (CODE 216)

The valve controller can be programmed for a standard valve (factory default) or reverse valve.

Note: The red CLOSED LED must be flashing to change the program.

1. Use the OPEN button to set the first digit of code 216, two green LEDs on. Each time the OPEN button

is pressed the next green LED will go on.

Note: If an error is made when entering the code, continue to press the OPEN button until all 9

LEDs are on, press again and the LEDs will all be off, press to return to the first LED on.

2. Press the CLOSE button to move the cursor to the next digit. Now all LEDs will be off and ready for the

second digit to be entered. Press the OPEN button once, one green LED on.

3. Press the CLOSE button to move the cursor to the next digit. All LEDs will be off. Press the OPEN

button 6 times, six green LEDs on.

4. After 3 seconds, the LEDs will indicate the valve type. One (1) LED is for a standard valve, two (2) LEDs

is for a reverse valve.

5. Press the OPEN button to change this setting.

6. Press the PRESET button for 3 seconds to exit. ALL LEDs will go off to indicate the data is accepted and

the control module returns to normal operation after 2 seconds.

7. All LEDs will flash if there is a problem with exiting the programming mode. Press any button to cancel

the warning or let time out after 10 seconds.