Xiii. programming (uics2), Error code e202, Programming mode – Elkhart Brass Unibody Valve User Manual

Page 59: Primary control and display module, Remote control and display module, Program primary or remote (code 2120)

Advertising
background image

59

800.346.0250 • www.elkhartbrass.com

XIII. PROGRAMMING (UICS2)

When in the program access mode the digital display will show operator inputs and program options. To gain

access to the program features a 4-digit program code must be entered.

Error Code E202

If error code E202 is shown it means that an invalid program code has been entered. Re-enter
program code when the digital display resets.

Programming Mode

Note: The valve must be closed and the red CLOSED LED must be on to program the valve control.

Press and hold the CLOSE button then press and hold the OPEN button. After 5 seconds the pressure display

shows ENTER/CODE. The program code can now be entered.

Primary Control and Display Module

Primary displays are programmed with the module function PRIMARY. A primary display receives input from the

valve and pressure sensor. When it is programmed with ID 0 it will not output information on to the datalink.

When it is programmed with ID 1 to ID 99 it will provide information (via the datalink) to remote displays.

Remote Control and Display Module

Remote displays are programmed with the module function REMOTE. A remote display must be programmed with

the same ID number as a primary display. It receives information for the display of valve position and pressure from

the primary display over the datalink. All program code features are programmed independently of the primary

display. No calibration is necessary on a remote display.

Program Primary or Remote (Code 2120)

This code sets the control and display module as a primary or remote. When a control is programmed as a

remote, the ID Number must be the same as the primary it is matched to.
1. Press and hold the OPEN and CLOSE buttons for five seconds.

Result: The PRESSURE display shows ENTER/CODE.

2. Enter code 2120

– Press OPEN button 2 times to enter 2

– Press CLOSE button to move the cursor to the next digit

– Press OPEN button 1 time to enter 1

– Press CLOSE button to move the cursor to the next digit

– Press OPEN button 2 times to enter 2.

Result: The PRESSURE display shows 2120.

3. After 3 seconds the current selection shows in the display PRIMARY or REMOTE.
4. Use the OPEN button to toggle between PRIMARY or REMOTE.
5. Press the CAF SELECT button and hold for 5 seconds to exit and save the programmed

parameters.

Advertising