ELKHART BRASS MANUFACTURING COMPANY, INC

C) Gear and Electric Actuator

1. Disassemble gear case cover from gear case by removing four screws as shown below.

Figure 10

2. Remove the 1/2" bolt and washer that locks the actuator assembly in position. Remove

actuator shaft. Remove gear sector and place in the full clockwise position as shown in

Figure 11. This equates to the valve open position for electric actuators on all valves

except EB_J & EB_S butterfly valves (The gear sector positions are opposite for the EB_J

and EB_S butterflys with electric actuators). This full clockwise position also equates to

the closed position for gear actuators on all valves.

Place gear sector

in full clockwise

position

Remove 1/2"

bolt and

washer

Figure 11

Close (Electric)

Open (Gear OP, EB_J & EB_S)

Open (Electric)

Close (Gear OP, EB_J & EB_S)

Remove

four

screws

Advertising