7 step 5: controlling applications via terminals, 9400 technology applications | electronic gearbox – Lenze E94AxHE Technology Application Electronic gearbox User Manual

Page 33

Advertising
background image

EDS94TA10030xxxx EN 1.2 - 11/2009

L

33

9400 Technology applications | Electronic gearbox

Short setup

Step 5: Controlling applications via terminals

4.7

Step 5: Controlling applications via terminals

Terminal assignment

Procedure

1. Enable controller: Set digital input RFR to HIGH level.
2. Deactivate quick stop: Set digital input DI1 to HIGH level.

Terminal

Assignment (Lenze setting)

X5

RFR

Controller enable

DI1

Quick stop

• If DI1 is set to LOW level, the drive is decelerated to standstill within the deceleration

time set for the quick stop function independent of the setpoint selection.

• If the quick stop function is deactivated, the drive is led to the selected setpoint again via

the set acceleration time.

DI2

Connection of reference switch

DI3

-

DI4

Close clutch

DI5

Reset error

• By means of a LOW-HIGH edge an existing error status can be reset if the cause of the

fault is removed.

DI6

-

DI7

-

DI8

-