‎Chapter 8 Configuring Recorders

Configuring the Fault Recorder

104

PM180 Substation Automation Unit

Option

Range

Default

Description

2nd Signaling
Frequency

110-3000 Hz

191.0 Hz

Specifies the mains signaling frequency for the
compliance evaluation

3rd Signaling
Frequency

110-3000 Hz

217.0 Hz

Specifies the mains signaling frequency for the
compliance evaluation

4th Signaling
Frequency

110-3000 Hz

317.0 Hz

Specifies the mains signaling frequency for the
compliance evaluation

Clearing EN50160 Evaluation Counters

To clear the present contents of the EN50160 evaluation counters before starting
your EN50160 evaluation, check the On-line button, select Reset from the Monitor
menu, and then Click on the “Clear EN50160 Counters” button (for more information,
see

Resetting Accumulators and Clearing Log Files

).

Configuring the Fault Recorder

The Fault recorder automatically records all fault events to the Fault log and to the
Sequence-of-Events log files. It can be triggered via the embedded fault detector, or
externally through any of the 48 digital inputs.
The Fault recorder can be globally disabled or enabled in your device.
The Fault recorder setup allows you to adjust thresholds and hysteresis for different
fault triggers, and to define the waveform and data log options for synchronous
recording during the fault events.
To configure the Fault recorder:

1. Select Memory/Log from the Meter Setup menu, and then click on

the Fault Recorder tab.

2. Enable fault triggers suitable for your application. Each one,

except of the external digital triggers, must be individually enabled
for the Fault recorder.

3. If you wish to change the default settings, adjust thresholds and

hysteresis for your fault triggers.

4. Select the waveform and data logging options for fault events.
5. Download your setup to the device.

The following table lists available Fault recorder options: