SATEC PM180 Operation Manual User Manual

Page 38

Advertising
background image

‎Chapter 3 Using the RDM

Configuring the PM180

36

PM180 Substation Automation Unit

Label

Option

Range

Default

Description

ConF

Wiring connection mode
(configuration)

See Table
below

4Ln3

The wiring connection of the device

Pt

1

V1-V3 PT ratio

1.0 - 6500.0 1.0

The phase potential transformer ratio
(primary to secondary ratio)

Pt.SEc

V1-V3 PT secondary

10 - 690 V

120

The phase potential transformer’s
secondary phase-to-phase voltage

Pt.4

1

V4 PT ratio

1.0 - 6500.0 1.0

The V4 potential transformer ratio
(primary to secondary ratio)

Pt.4SEc

V4 PT secondary

10 - 690 V

120

The V4 potential transformer’s secondary
voltage

Ct

2

I1-I3 CT primary current 1 - 10000 A 5

The primary rating of the phase current
transformer on standard (20A/10A) inputs

Ct.SEc

2

I1-I3 CT secondary
current

1, 5 A

5

The secondary rating of the phase current
transformer on standard (20A/10A) inputs

Ct.4

2

I4 CT primary current

1-10000 A

5

The primary rating of the I4 current
transformer on standard (20A/10A) inputs

Ct.4SEc

2

I4 CT secondary current 1, 5 A

5

The secondary rating of the I4 current
transformer on standard (20A/10A) inputs

Ct.E.

2

I1x-I3x CT primary
current

1 - 10000 A 5

The primary rating of the phase current
transformer on extended (100A) inputs

Ct.E.SEc

2

I1x-I3x CT secondary
current

1, 5 A

5

The secondary rating of the phase current
transformer on extended (100A) inputs

Ct.4.E.

2

I4x CT primary current

1 - 10000 A 5

The primary rating of the I4x current
transformer on extended (100A) inputs

Ct.4.E.SEc

2

I4x CT secondary

current

1, 5 A

5

The secondary rating of the I4x current
transformer on extended (100A) inputs

U.dC.

VDC nominal voltage

10-300 V

125

The nominal VDC voltage

FrEq

Nominal frequency

50, 60 Hz

50 (60 for
North
America)

The nominal power frequency

PH.Ord.

Phase order

AbC, ACb

AbC

The normal phase sequence

Ld C

I1-I3 Maximum demand
load current

0 - 10000 A 0

The maximum demand load current for I1-
I3 current inputs (0 = CT primary)

Ld C4

I4 Maximum demand
load current

0 - 10000 A 0

The maximum demand load current for
the I4 current input (0 = CT primary)

Ld C.E.

I1x-I3x Maximum
demand load current

0 - 10000 A 0

The maximum demand load current for
I1x-I3x current inputs (0 = CT primary)

Ld C4.E.

I4x Maximum demand
load current

0 - 10000 A 0

The maximum demand load current for
the I4x current input (0 = CT primary)

1

PT Ratio is defined as a relation of the potential transformer’s primary voltage

ratin

g to its secondary rating. For example, if your potential transformer’s primary

rating is 14400V and the secondary rating is 120V, then the PT Ratio = 14400/120 =
120.
Available wiring modes are listed in the following table.

Wiring
Mode

Description

3OP2

3-wire Open Delta using 2 CTs (2 element)

4Ln3

4-wire Wye using 3 PTs (3 element), line-to-neutral voltage readings

3dir2

3-wire Direct Connection using 2 CTs (2 element)

4LL3

4-wire Wye using 3 PTs (3 element), line-to-line voltage readings

3OP3

3-wire Open Delta using 3 CTs (2½ element)

3Ln3

4-wire Wye using 2 PTs (2½ element), line-to-neutral voltage readings

3LL3

4-wire Wye using 2 PTs (2½ element), line-to-line voltage readings

3bLn3

3-wire Broken Delta using 2 PTs, 3 CTs (2½-element), line-to-neutral voltage readings

3bLn3

3-wire Broken Delta using 2 PTs, 3 CTs (2½-element), line-to-line voltage readings

To select a setup option:

1. Press SELECT to activate the middle window.
2. Use the Up/Down arrow keys to scroll to the desired option.

To change the display option:

1. Press SELECT to activate the lower window.