‎Chapter 8 Configuring Recorders

Configuring the EN50160 Power

Quality Recorder

PM180 Substation Automation Unit

93

Indicatives
Values

For the remaining characteristics of the voltage, by their unpredictable nature, the
standard gives only indicative values, which are intended to provide users with
information on the expected order of magnitude.
The following table gives the characteristics for which indicative values have been
specified by the standard.

Voltage
Characteristic

Indicative values

Observation
period

Voltage dips

Less than 1 s, 60% depth

Year

Short interruptions

70% less than 1 s

Year

Long interruptions

10 to 50% less than 3 min

Year

Temporary overvoltages

Less than 1.5 kV RMS

Year

Transient overvoltages

Less than 6 kV peak

Year

Resources

CENELEC publications:

EN 50160:1999 Voltage characteristics of electricity supplied by public distribution
systems
IEC publications:

IEC 61000-4-7:2002 Electromagnetic compatibility (EMC)

– Part 4-7 Testing and

measurement techniques

– General guide on harmonics and interharmonics

measurements and instrumentation, for power supply systems and equipment
connected thereto,

IEC 61000-4-15:2003 Electromagnetic compatibility (EMC)

– Part 4 Testing and

measurement techniques

– Section 15: Flickermeter – Functional and design

specifications
IEC 61000-4-30:2003 Electromagnetic compatibility (EMC)

– Part 4-30 Testing and

measurement techniques

– Power quality measurement methods

Eurelectric (Union of the Electricity Industry) publications:

Application guide to the European Standard EN 50160 on Voltage characteristics of
electricity supplied by public distribution systems, Ref: 23002 Ren9530, July 1995
Measurement guide for voltage characteristics, Ref: 23002 Ren9531, July 1995

Voltage characteristic

Compliance with stated
limits, % of time

Observation
period

Power frequency

1% for 95% of a week

1% for 99.5% of a year

+4/-6% for 100% of time

Week, year

Voltage variations (supply
voltage magnitude)

10% Un for 95% of time

Week

Rapid voltage changes

4-5% Un (up to 10% Un)

Day

Flicker (fluctuations of
voltage magnitude)

Plt

1 for 95% of time

Week

Voltage unbalance

2-3% for 95% of time

Week

Harmonic voltage

THD

8 for 95% of time

Week

Interharmonic voltage

To be defined

Week

Mains signaling voltage

Within “Meister-curve” for
99% of time

Day