Configuring dnp3, Dnp options – SATEC PM180 Operation Manual User Manual

Page 113

Advertising
background image

‎Chapter

10

Configuring

Communication Protocols

Configuring DNP3

PM180 Substation Automation Unit

111

1. From the Meter Setup menu select Protocol Setup and click on the

Modbus Registers tab.

2. Change the raw scales in the Modbus Options pane. The

allowable range is 0 to 65535.

3. Click Send to download your setup to the device.

Configuring DNP3

DNP Options can be changed both via DNP3 and Modbus. Refer to the PM180
DNP3 Reference guide for information on the protocol implementation and a list of
the available data points.

DNP Options

From the Meter Setup menu select Protocol Setup and click on the DNP Options tab.

The following table describes available DNP options. Refer to the DNP3 Data Object
Library document available from the DNP

User’s Group on the DNP3 object types.

Parameter

Options

Default

Description

Binary Inputs (BI)

Number of BI to
Generate
events

0-64

3

21

The total number of BI change event
points for monitoring

Binary Input
Object

Single-bit

With Status

Single-bit

The default BI object variation for
requests with qualifier code 06 when no
specific variation is requested

Binary Input
Change Event
Object

Without Time

With Time

With Time

The default BI change event object
variation for requests with qualifier code
06 when no specific variation is
requested

Analog Inputs (AI)

Number of AI to
Generate
events

0-64

3

43

The total number of AI change event
points for monitoring