‎Appendix E Data Scales










PM180 Substation Automation Unit

181

Appendix E Data Scales

The maximum values for volts, amps and power in the PM180 setup and in
communications are limited by the voltage and current scale settings. See

Advanced

Device Setup

in Chapter 7 on how to change the voltage and current scales in your

device.
The following table shows the device data scales.

Scale

Conditions

Range

Maximum voltage (V max)

All configurations

Voltage scale

PT Ratio, V

1

Maximum current (I max)

All configurations

Current scale

CT Ratio, A

2, 3

Maximum fault current (Ix max)

All configurations

30

CT primary current, A

Maximum Power (P max)

4

All configurations

V max

I max

2, W

Maximum frequency

50 or 60 Hz

100 Hz

1

The default voltage scale is 828V. The recommended voltage scale is

120V+20% = 144V for using with external PT’s, and 690V+20% = 828V for a

direct connection to power line.

2

CT Ratio = CT primary current/CT secondary current

3

The default current scale is 2

CT secondary for the IEC current input option

(2.0A with 1A secondaries and 10.0A with 5A secondaries), and 4

CT

secondary for the ANSI current input option (4.0A with 1A secondaries and

20.0A with 5A secondaries).

4

Maximum power is rounded to whole kilowatts. With PT=1.0, it is limited to

9,999,000 W.

Advertising