‎Chapter 1 Introduction

PM180 Substation Automation Unit

9

AC/DC Inputs

The PM180 is provided with a set of fully isolated AC/DC inputs for connecting to the
AC feeders or station battery:

Three isolated AC voltage inputs (up to 690VAC direct line-to-
line input voltage)

Four standard isolated AC current inputs with an extended
input range up to 2000% overload (10A/20A input currents, to
100 Amps fault currents)

One AC/DC voltage input (up to 400VAC/300VDC) for
monitoring the station battery

Digital and Analog I/O module Options

The PM180 has three I/O expansion slots for hot-swap plug-in I/O modules. The
following I/O options are available:

16 DI x 3

– up to three 16-channel digital input modules: 16

optically isolated inputs per module; options for dry contacts,
10-30V, 20-250V wet inputs; programmable de-bounce time
from 1 ms to 1 sec; free linkage to Sequence-of-Events
recorder, Fault recorder, control setpoints, pulse counters and
Energy/TOU subsystem.

8 RO x 3

– up to three 8-channel relay output modules: eight

relays per module; unlatched, latched and pulse operations,
failsafe operation for alarm notifications; programmable pulse
width; direct remote relay control through communications.

4 AI/AO x 2

– up to two combined 4-channel AI/AO modules:

four optically isolated analog inputs and four analog outputs
per module with internal power supply; options for 0-1mA,
±1mA, 0-20mA, 4-20mA, 0-50mA and ± 10V inputs and
outputs; 100% overload currents for 0-1mA and ±1mA AI/AO
(0-2 mA and ±2 mA ranges are available).

Communications Options

The PM180 has extensive communications capabilities:

Standard communication ports

Three independent universal serial communications ports
(RS-232/485, RS-422/485 and RS-485, up to 115,200 bps,
MODBUS RTU/ASCII and DNP3.0 protocols)

Infrared port (MODBUS RTU/ASCII and DNP3.0 protocols)

Ethernet 10/100Base-T port (MODBUS/TCP, DNP3.0/TCP
and IEC 61850 protocols (up to five non-intrusive
simultaneous connections, Telnet service port)

USB 1.1 port (MODBUS RTU protocol, 12 Mbps) for fast local
communications and data retrieving

Optional communication ports

The PM180 has three expansion slots for hot-swap plug-in communication modules.
In addition, each COM module is equipped with a serial RS-422/485 communication
port. The following COM module options are available:

Embedded 56K modem for communications through public
telephone lines (MODBUS RTU/ASCII and DNP3.0 protocols)

Embedded Cellular modem for communication through public
cellular network (MODBUS/TCP and DNP3.0/TCP)

10/100Base TX or 100Base FX (optical port) backup Ethernet
port (MODBUS/TCP, DNP3.0/TCP and IEC 61850 protocols,