‎Appendix C Parameters for Monitoring and Data Logging










156

PM180 Substation Automation Unit

Appendix C Parameters for Monitoring and

Data Logging

The following table lists parameters measured by the PM180 that are available for
monitoring via communication ports, for data logging, and for triggering setpoints.

Designation

Description

NONE

None (stub, read as zero)

SETPOINTS

Setpoint Status

SP1:32

Setpoints 1-32

SPECIAL INPUTS

Special Inputs (setpoint triggers only)

VOLT DISTURB

Voltage disturbance

– waveshape fault. See

Using the Voltage

Disturbance Trigger

.

PHASE ROTATION

Phase rotation order

EVENT FLAGS

User Event Flags

EVENT FLAG 1:16

Event Flags 1-16

STATIC EVENTS

Internal Static Events (setpoint triggers only)

PHASE ORDER ERR

Phase order error

POS PHASE ORDER

Positive (ABC) phase order

NEG PHASE ORDER

Negative (ACB) phase order

PQ EVENT

PQ event. See

Power Quality Event Indication and Cross Triggering

.

FAULT EVENT

General fault event: fault recorder has been triggered. See

Fault

Indication and Cross Triggering

.

FAULT DETECTED

The embedded fault detector has detected a fault. See

Fault Indication

and Cross Triggering

.

EXTERNAL TRIGGER

Fault recorder has been triggered via a digital input. See

Fault Indication

and Cross Triggering

.

DEVICE FAULT

Device fault (non-critical error). See

Device Fault Alarm

.

NO VOLTAGE

No measured voltage

PULSED EVENTS

Internal Pulsed Events (setpoint triggers only)

kWh IMP PULSE

kWh Import pulse

kWh EXP PULSE

kWh Export pulse

kWh TOT PULSE

kWh Total pulse

kvarh IMP PULSE

kvarh Import pulse

kvarh EXP PULSE

kvarh Export pulse

kvarh TOT PULSE

kvarh Total pulse

kVAh PULSE

kVAh pulse

START DMD INT

Start of power demand interval pulse

START TRF INT

Start of tariff interval pulse

EXT TRIGGERS

External Trigger Events (setpoint triggers only)

EXT TRIGGER 1:16

External cross triggering channel 1-16 (UDP broadcast trigger
message). See

Cross Triggering Setpoints

.

TIMERS

Interval Timers (setpoint triggers only)

TIMER 1:16

Interval timer 1-16

DIGITAL INPUTS

Digital Inputs

DI1:48

Digital input status DI1:DI48

PULSE INPUTS

Pulse Inputs (setpoint triggers only)

DI1:48

Transition pulse on a digital input DI1:DI48

RELAYS

Relays

RO1:16

Relay status RO1:RO2

COUNTERS

Pulse Counters

COUNTER 1:32

Pulse counter 1-32

TIME

Time/Date Parameters (setpoint triggers only)

DATE

Date (DDMMYY)

TIME

Time (HHMMSS)

DAY OF WEEK

Day of week