Chapter 10 configuring communication protocols, Configuring modbus, Modbus point mapping – SATEC PM180 Operation Manual User Manual

Page 112: Changing raw scales for 16-bit registers

Advertising
background image

‎Chapter 10 Configuring Communication
Protocols

Configuring MODBUS

110

PM180 Substation Automation Unit

Chapter 10 Configuring Communication

Protocols

This section describes how to customize protocol options for use with your
application software.

Configuring MODBUS

MODBUS Point Mapping

The PM180 provides 120 user assignable registers in the address range of 0 to 119.
You can re-map any register available in the device to any assignable register so that
Modbus registers that reside at different locations may be simply accessed using a
single request by re-mapping them to adjacent addresses.
Initially these registers are reserved and none of them points to an actual data
register. To build your own MODBUS register map:

1. From the Meter Setup menu select Protocol Setup and click on the

MODBUS Registers tab.

2. Click on the Default button to cause the assignable registers to

reference the actual default device register 11776 (0 through 119
are not allowable register addresses for re-mapping).

3. Type in the actual addresses you want to read from or write to via

the assignable registers. Refer to the PM180 MODBUS Reference

Guide for a list of the available registers. Note that 32-bit
MODBUS registers should always start at an even register
address.

PM180_USB – Protocol Setup

4. Click Send to download your setup to the

device.

Changing Raw Scales for 16-bit Registers

16-bit analog registers are normally read with scaling to the default range of 0 to
9999. Refer to the PM180 MODBUS Reference Guide for more information on
scaling 16-bit MODBUS registers.
To change the default low and high raw scales: