‎Appendix D EN50160 Statistics Log Files










178

PM180 Substation Automation Unit

Field
No.

Designation

Description

16

V1 N1

Total number of incidents on phase V1

17

V1 Max

Maximum voltage magnitude on phase V1

18

V2 N1

Total number of incidents on phase V2

19

V2 Max

Maximum voltage magnitude on phase V2

20

V3 N1

Total number of incidents on phase V3

21

V3 Max

Maximum voltage magnitude on phase V3

Transient Overvoltages (indicative statistics)

1

N1 110%

Number of polyphase incidents u>120%

2

N2 150%

Number of polyphase incidents u>150%

3

N3 200%

Number of polyphase incidents u>200%

4

N4 250%

Number of polyphase incidents u>250%

5

N5 300%

Number of polyphase incidents u>300%

6

V1 N1 110%

Number of incidents u>120% on phase V1

7

V1 N2 150%

Number of incidents u>150% on phase V1

8

V1 N3 200%

Number of incidents u>200% on phase V1

9

V1 N4 250%

Number of incidents u>250% on phase V1

10

V1 N5 300%

Number of incidents u>300% on phase V1

11

V2 N1 110%

Number of incidents u>120% on phase V2

12

V2 N2 150%

Number of incidents u>150% on phase V2

13

V2 N3 200%

Number of incidents u>200% on phase V2

14

V2 N4 250%

Number of incidents u>250% on phase V2

15

V2 N5 300%

Number of incidents u>300% on phase V2

16

V3 N1 110%

Number of incidents u>120% on phase V3

17

V3 N2 150%

Number of incidents u>150% on phase V3

18

V3 N3 200%

Number of incidents u>200% on phase V3

19

V3 N4 250%

Number of incidents u>250% on phase V3

20

V3 N5 300%

Number of incidents u>300% on phase V3

21

V1 Peak Max

Maximum peak voltage on phase V1

22

V2 Peak Max

Maximum peak voltage on phase V2

23

V3 Peak Max

Maximum peak voltage on phase V3

Supply Voltage Unbalance

1

Nnv

Number of non-valid 10-min intervals

2

N

Number of valid 10-min intervals

3

N1

Number of incidents V Unb > 2%, N1

4

N1/N, %

EN50160 compliance ratio, N1/N

5

V Unb% Max

Maximum voltage unbalance

Harmonic Voltage

1

Nnv

Number of non-valid 10-min intervals

2

N

Number of valid 10-min intervals

3

N1

Number of polyphase harmonic voltage incidents, N1

4

N2

Number of polyphase voltage THD incidents, N2

5

N1/N, %

EN50160 harmonic voltage compliance ratio, N1/N

6

N2/N, %

EN50160 voltage THD compliance ratio, N2/N

7

V1 N1

Number of harmonic voltage incidents on phase V1

8

V1 N2

Number of voltage THD incidents on phase V1

9

V1 HD% Max

Worst-case harmonic magnitude on phase V1, %Un

10

V1 H#

Worst-case harmonic component number on phase V1

11

V1 THD Max

Worst-case voltage THD on phase V1

12

V2 N1

Number of harmonic voltage incidents on phase V2

13

V2 N2

Number of voltage THD incidents on phase V2

14

V2 HD% Max

Worst-case harmonic magnitude on phase V2, %Un

15

V2 H#

Worst-case harmonic component number on phase V2

16

V2 THD Max

Worst-case voltage THD on phase V2

17

V3 N1

Number of harmonic voltage incidents on phase V3

18

V3 N2

Number of voltage THD incidents on phase V3