Appendix f device diagnostic codes, Device, Diagnostic codes – SATEC PM180 Operation Manual User Manual

Page 184: Device diagnostic codes

Advertising
background image

‎Appendix F Device Diagnostic Codes










182

PM180 Substation Automation Unit

Appendix F Device Diagnostic Codes


Diagnostic
Code

Description

Reason

0

Critical error

Unrecoverable system failure - device
operation stops

1

Permanent fault (critical error)

Repeated unrecoverable failure

2

Memory/Data error

Hardware failure

3

Hardware watchdog reset

Hardware failure

4

DSP/Sampling fault

Hardware failure

5

CPU exception

Hardware failure

7

Software watchdog timeout

Hardware failure

8

Power down/Up

Loss of power

9

Warm restart/Device reset

External restart via communications or
by firmware upgrade

10

Configuration reset

Corrupted setup data has been
replaced with the default configuration

11

RTC fault (critical error)

The clock time has been lost

12

Configuration fault (critical error)

Factory, calibration or basic device
configuration data has been corrupted

14

Expanded memory fault

Hardware failure

15

CPU EEPROM fault

Hardware failure

16

AC board EEPROM fault

Hardware failure

17

I/O board EEPROM fault

Hardware failure

20

C Library error

Hardware failure

21

RTOS Kernel error

Hardware failure

22

Task error

Hardware failure

24

IRIG-B signal lost

No IRIG-B signal from the GPS master
clock. Cleared automatically when the
IRIG-B signal is detected.

25

IRIG-B time unlocked

The GPS master clock has lost the
satellite signal. Cleared automatically
when the satellite signal is locked.

NOTE

A critical error is an unrecoverable hardware or configuration failure that causes the
device to release all its outputs and to stop normal operation until the critical error is
cleared.
See

Device Diagnostics

for more information on the PM180 built-in diagnostics. See

Viewing and Clearing Device Diagnostics

in Chapter 11,

Viewing and Clearing

Device Diagnostics

in Chapter 4, and

Status Information Display

in Chapter 3 on how

to inspect and clear the device diagnostics.