Device options menu – SATEC PM180 Operation Manual User Manual

Page 40

Advertising
background image

‎Chapter 3 Using the RDM

Configuring the PM180

38

PM180 Substation Automation Unit

The following table lists available port options, their default settings and ranges.

Label

Option

Range

Default

Prot

Communications protocol

rtu - MODBUS RTU

ASCII - MODBUS ASCII

dnP3 - DNP3.0

rtu

rS

Port interface

232, 422, 485

232 (COM1)

485 (COM2/3)

Addr

Device address

1-247 (MODBUS)

1-255 (DNP3.0)

1

bAud

Baud rate

300-115200 bps

19200

dAtA

Data format

7E, 8n, 8E

8n

To select a port option:

1. Press SELECT to activate the middle window.
2. Use the Up/Down arrow keys to scroll to the

desired option.

To change the port option:

1. Press SELECT to activate the lower window.
2. Use the Up/Down arrow keys to set the desired option.
3. Press ENTER to confirm your changes and to store your new

setting, or press ESC to discard changes.

To exit the menu:
From the middle window, press ESC or ENTER.

Device Options Menu

This menu allows you to select some user-configurable device options or put the
device into energy test mode. To enter the menu, select “OPtS’ from the menu list.
The following table lists available device options, their default settings and ranges.

Label

Option

Range

Default

Description

P.cAL

Power calculation
mode

rEAc (using reactive power),
nAct (using non-active
power)

rEAc

The method used for calculating
reactive and apparent powers (see
“Power Calculation Modes” in

Advanced Device Setup

, Chapter 7)

roLL

Energy roll value

10.E4 = 10,000 kWh

10.E5 = 100,000 kWh

10.E6 = 1,000,000 kWh

10.E7 = 10,000,000 kWh

10.E8 = 100,000,000 kWh

10.E9 =1,000,000,000 kWh

10.E9

The value at which energy counters
roll over to zero

test

Energy test mode OFF, On

OFF

Setting this option to On puts the
device into the energy test mode

To select a menu option:

1. Press SELECT to activate the middle window.
2. Use the Up/Down arrow keys to scroll to the desired option.

To change the option:

1. Press SELECT to activate the lower window.
2. Use the Up/Down arrow keys to set the desired option.
3. Press ENTER to confirm your changes and to store your new

setting, or press ESC to discard changes.

To exit the menu:
From the middle window, press ESC or ENTER.

OPtS

rEAc

P.cAL

SELECT

ENERGY

ENTER

ENERGY

ENTER

CHG

OPtS