Configuring the event recorder, Configuring data log files, Configuring the – SATEC PM180 Operation Manual User Manual

Page 84: Event recorder

Advertising
background image

‎Chapter 8 Configuring Recorders

Configuring the Event Recorder

82

PM180 Substation Automation Unit

No. File

Type

Size,
Bytes

Sections/
Channel

Max. of
Records

Max. of
Events

Description

10

Data log #9 Wrap

around

474240

12

260

260

Configured for
EN50160
compliance
statistics

11

Data log
#10

Wrap
around

174720

3

260

260

Configured for
EN50160
harmonics survey

14

Data log
#13 (fault
data trend)

Wrap
around

560000

10000

10000

Used by the Fault
recorder

15

Data log
#14

(PQ data
trend)

Wrap
around

520000

10000

10000

Used by the PQ
recorder

24

Waveform
log #7

Wrap
around

42880000 10

4000

1000

Used by the PQ and
Fault recorders

25

Waveform
log #8

Wrap
around

17152000 8

2000

500

Used by the PQ
recorder

26

SOE log

Wrap
around

160000

10000

10000

27

PQ log

Wrap
around

640000

20000

20000

28

Fault log

Wrap
around

440000

10000

10000

Configuring the Event Recorder

To change the Event log file size:

1. Select Memory/Log from the Meter Setup menu, and then click on

the Log Memory tab.

2. Double click on the Event log file partition with the left mouse

button.

3. Select a file type.
4. Select the maximum number of records you want to be recorded in

the file.

5. Click OK, and then send your new setup to the device or save to

the device database.

By default, the Event recorder stores all events related to configuration changes,
reset, and device diagnostics. In addition, it records events related to setpoint
operations. Each setpoint should be individually enabled for recording to the Event
log.
To log setpoint operations, add the “Event log” action to the setpoint actions list. Put
the event log action at the beginning of the list to allow other recorders to use the
sequence number assigned to the event for cross-linking between records logged to
different files. When a setpoint event happens, the Event recorder logs all setpoint

Advertising