‎Chapter 9 Totalization Energy and
TOU Registers

Configuring Summary and TOU

Registers

PM180 Substation Automation Unit

107

Chapter 9 Totalization Energy and TOU

Registers

The PM180 provides 16 summary energy registers and 16 parallel TOU energy and
maximum demand registers to link to any internal energy source or to any external
pulse source that delivers energy pulses through the device digital inputs.
A total of 64 energy sources can be connected to the summary and TOU registers.
Each summary register can accumulate energies from multiple sources using
arithmetic addition and subtraction. A summary register may be linked to another
summary register to provide more comprehensive energy calculations.
The TOU system provides for each TOU energy register a parallel maximum demand
register that is updated automatically when a corresponding TOU register is
activated. The device supports 16 different tariffs using an arbitrary tariff structure.
The PM180 TOU system technique is based on the currently active TOU annual
calendar that assigns the user-selectable daily profile to each day of the year. The
TOU daily profiles specify daily tariff change points. The PM180 memory stores
calendars for 10 years. A total of 16 types of days are supported with up to eight tariff
changes per day.
By default, the summary registers in your device are not linked to energy sources
and are not operational. To activate a summary energy register, link it to the energy
source(s).
To activate TOU system:

1. Configure the TOU daily profiles for different types of days.
2. Configure the TOU calendars.
3. Link the TOU registers to the corresponding summary energy

registers that are used as source registers for TOU system.

Configuring Summary and TOU Registers

To configure the device summary and TOU registers, select Energy/TOU from the
Meter Setup menu.

The available options are described in the following table:

Option

Format/Range

Default

Description

Summary Energy/TOU Registers

Roll over

1 to 1,000,000,000

1,000,000,000 The value at which the accumulator

register rolls over to zero