Demand setup menu, Communication setup menus – SATEC PM180 Operation Manual User Manual

Page 39

Advertising
background image

‎Chapter 3 Using the RDM

Configuring the PM180

PM180 Substation Automation Unit

37

2. Use the Up/Down arrow keys to set the desired option.
3. Press ENTER to confirm your changes and to store your new

setting, or press ESC to discard changes.

To exit the menu:
From the middle window, press ESC or ENTER.

Notes

1. Always specify the wiring mode and transformer ratings prior to setting up setpoints and
triggers for the fault and power quality recorders.

2. The maximum value for the product of the phase CT primary current and PT ration is
10,000,000. If the product is greater, the powers and power factors are zeroed.

Demand Setup Menu

This menu allows you to configure the time parameters for calculating power,
ampere, volt and harmonic demands. To enter the Basic Setup menu, select “dnd”
from the menu list.
The following table lists available options, their default settings and ranges.

Label

Option

Range

Default

Description

P.dP

Power demand period

1, 2, 5, 10,
15, 20, 30, 60
min

15

The length of the demand period for
power demand calculations

n.P.dP

The number of demand
periods in the sliding
window

1-15

1

The number of demand periods to be
averaged for sliding window demands

d.Snc.In Power demand sync

source

Clc (device
clock), di.In.1
- di.In.48
(digital input
1-48)

Clc

The source input for synchronization of
the demand intervals. If a digital input is
specified as the source, a pulse front
denotes the start of the demand interval

A.dP

Ampere demand period 0 - 9000 sec

900

The length of the demand period for
ampere demand calculations

U.dP

Volt demand period

0 - 9000 sec

900

The length of the demand period for volt
demand calculations

H.dP

Harmonic demand
period

0 - 9000 sec

900

The length of the demand period for
harmonic demand calculations

To select an option:

1. Press SELECT to activate the middle window.
2. Use the Up/Down arrow keys to scroll to the desired option.

To change the option:

1. Press SELECT to activate the lower window.
2. Use the Up/Down arrow keys to set the desired option.
3. Press ENTER to confirm your changes and to store your new

setting, or press ESC to discard changes.

To exit the menu:
From the middle window, press ESC or ENTER.

Communication Setup Menus

These three menus allow you to configure the main settings for ports COM1-COM3.
Additional settings such as delays and timeouts can be configured through
HyperTerminal. To enter the desired Port Setup menu for ports COM1-COM3, select
“Port.1”, “Port.2” or “Port.3’ from the menu list.