‎Chapter 8 Configuring Recorders

Configuring the Waveform Recorder

88

PM180 Substation Automation Unit

The total number of records you must allocate to store the required
number of events (series) is defined as follows:

Number of Records = Number of Records per Series x Number of

Series

For example, if you want to record a 64-cycle waveform sampled
at a rate of 32 samples per cycle, the number of records required
for one waveform series would be:

Number of Records per Series = (32 x 64)/512 = 4.

If you want to allocate space sufficient to store 20 waveform
events (series), you should set up the waveform log file for 4 x 20
= 80 records.

5. Click OK, and send your setup to the device or save to the

database.

6. Click “Setup Recorder”, or click on the “Waveform Recorder” tab.

The following table lists available waveform options.

Option

Range

Description

Samples per Cycle

32, 64, 128, 256 samples/cycle

Defines the sampling rate for the
waveform log

Cycles per Series

16-10848 (32 samples/cycle),
8-5424 (64 samples/cycle),

4-2712 (128 samples/cycle)

2-1356 (256 samples/cycle)

Defines the total duration of the
waveform recording per event/series

Before Cycles

1-20

Defines the number of cycles to be
recorded prior to the event

Num. of Channels

1-26

The number of the simultaneously
recorded channels

7. Select the sampling rate for waveforms.
8. Select the number of cycles to be recorded prior to the event, and

a total number of cycles in the waveform.

9. Add the name for your waveform log file in the “Name” box. It will

appear in the waveform reports.