Wire the powermonitor 1000 unit, Voltage sensing – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 10

Advertising
background image

10 PowerMonitor 1000 Unit

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

Wire the PowerMonitor 1000 Unit

The power monitor has finger-safe screw terminals with pressure plates for all wiring

connections.

Terminal Block Layout

Voltage Sensing

The PowerMonitor 1000 unit monitors a variety of three-phase and single-phase circuits.

Voltages of up to 600V AC line-to-line (347V AC line-to-ground) may be connected directly.

Higher voltages require potential transformers (PTs), also known as voltage transformers (VTs).
Wiring must conform to all applicable codes and standards. In particular, you must provide

suitable overcurrent protection with current and interrupting ratings selected to protect the

wiring.
Pay particular attention to correct phasing and polarity of voltage connections. The diagrams use

the dot convention to indicate transformer polarity. The dot indicates the H1 and X1 terminals

on the high side and low side of the transformer respectively.
When you wire a power monitor to existing PTs and metering devices, the voltage sensing

terminals of the power monitor must be connected in parallel with the voltage sensing terminals

of the existing metering devices.

The following wiring diagrams indicate typical voltage sensing connections to various types of

power systems.

Wire Type

Wire Size Range

Wires per Terminal

Recommended Torque

Cu - 75 °C (167 °F)

0.33…0.21 mm

2

(22 … 14 AWG)

2 max per terminal, sol-sol or

str-str only (no mixed pairs)

0.8 N•m (7 lb•in)

IMPORTANT

Ungrounded three-wire Delta systems with line-to-line voltages between 347…600V AC may be directly

connected. However, if a ground fault occurs that raises the line-to-ground voltage above 347V AC, the unit
indicates a voltage over-range condition.

V1

V2

V3

VN

I1+

I1-

I2+

I2-

I3+

I3-

S1

NC

S2

CF

SCOM

CF1

L2

L1

Y

K

Z

Advertising