Special wiring modes, 1pt 1ct line-to-line – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 17

Advertising
background image

PowerMonitor 1000 Unit 17

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

You can use two CTs only on three-wire systems.

Single-phase, Two-current Transformers

Special Wiring Modes

There are two special wiring modes for the power monitor.

1PT 1CT Line-to-line

This special wiring mode is designed for use in capacitor bank controllers. Traditional capacitor

bank control measures VBC and IA to calculate reactive power and power factor. In this mode,

the power monitor returns values as if it were configured in Delta mode. Three-phase values are

estimated assuming a balanced load.
The following wiring diagram indicates the connections for the 1PT 1CT Line-to-line mode. A

PT must be used. Wiring diagnostics are disabled in this mode.

Line

Load

Ground

L1

L2

N

Voltage Mode = Any

CTs (by user)

Shorting Terminal

Block (by user)

PowerMonitor 1000 Unit

I1+

I1-

I2+

I3+

I2-

I3-