Time of Use Logs

The power monitor maintains records of energy and demand organized by times of use you

define. These records may be used for billing and cost allocation by RSPowerPlus software.
There are up to three time-of-use (TOU) logs, one for real energy and demand, one for reactive

energy and demand, and one for apparent energy and demand. Within each log, energy

consumption and peak demand are recorded into off-peak, mid-peak, and on-peak categories.

The days and times that define the mid- and on-peak periods are user selectable. All times of use

not defined as mid- or on-peak are considered off-peak.
This function applies to catalog numbers 1408-EM1 (one TOU log, real energy only),

1408-EM2 (three TOU logs, energy, and demand), and 1408-EM3 (three TOU logs, energy,

and demand).

Logged Parameters

Each TOU log consists of 13 records, an in-process record for the current month, and one record

each for the previous 12 months. The monthly records operate in a circular or FIFO fashion. On

a user-selected day each month, the current record is pushed into the monthly record stack and

cleared. Each record contains the following data:

Net energy: off-peek, mid-peek, and on-peak

Peak demand: off-peek, mid-peek, and on-peak

Start and end date/time of the record

Record number

Results

Time of use log records can be accessed only via communication.

Commands

Store and clear current TOU Record

Clear TOU Log

Related Functions

Energy metering

Demand metering