Network time synchronization, Related functions – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 55

Advertising
background image

PowerMonitor 1000 Unit 55

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

Network Time Synchronization

Network time synchronization is available only on units equipped with the optional Ethernet

network. Set-up parameters are found in the Ethernet communication set-up menu. The power

monitor updates its time from a simple network time protocol (SNTP) server or an anycast

group of SNTP servers, depending on setup parameter values. Network-time synchronization

set-up parameters are found in the Ethernet communication set-up menu.

Related Functions

Demand metering

Data logging

Parameter

Description

Range

Default

User Setting

SNTP Mode

Select

0 = Disable

1 = Unicast – Specify the IP

address of a unicast SNTP server.

2 = Anycast mode – Specify the

broadcast IP address of a SNTP

anycast group.

0…2

0

SNTP Update

Interval

Defines how often the time is

updated from the SNTP server.

1…32766 minutes

300

Time Zone Select There are 32 available time zones.

0…32

7 (Eastern Time)

Time Server IP

Address

Unicast server or anycast group IP

address in format aaa.bbb.ccc.ddd.

0.0.0.0…

255.255.255.255

0.0.0.0

Advertising